MULTISPAN AVF-19N Product Manual Download Page 5

1) All safety related  codifications, symbols and instructions that appear in this operating manual 
       or on the equipment must be strictly followed to ensure the safety of the operating personnel as 
      well as the instrument. 

2) If all the equipment is not handled in a manner specified by the manufacturer, it might impair the 
     protection provided by the equipment .

=>

 Read complete instructions prior to installation and operation of the unit. 

WARNING

 : Risk of electric shock.

SafetyPrecautions

 3) Cable used for connection to power source, must have a cross section of 1mm or greater. These wires 
      should have insulations capacity made of at least 1.5kV.      

 2) To reduce electro magnetic interference, use wire with adequate rating and twists of the same of 
      equal size shall be made with shortest connection.            

 1) To prevent the risk of electric shock power supply to the equipment must be kept OFF while doing the 
      wiring arrangement. Do not touch the terminals while power is being supplied.  

 4) A better anti-noise effect can be expected by using standard power supply cable for
      the instrument.         

WarningGuidelines

2

1) This equipment, being built-in-type, normally becomes a part of main control panel and in such case the 
    terminals do not remain accessible to the end user after installation and internal wiring.  

2) Do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product 
     or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.      

3) Circuit  breaker or mains switch must be installed between power source and supply terminal to 
    facilitate power ‘ON’ or ‘OFF’ function. However this mains switch or circuit breaker must be 
     installed at convenient place normally accessible to the operator.     
4) Use and store the instrument within the specified ambient temperature and humidity ranges as 
     mentioned in this manual.     

InstallationGuidelines

MechanicalInstallation

1) Prepare the panel cutout with proper dimensions as show above.
2) Fit the unit into the panel with the help of clamp given.
3) The equipment in its installed state must not come in close proximity to any heating source, 
    caustic vapors, oils steam, or other unwanted process by products.
4) Use the specified size of crimp terminal (M3.5 screws) to wire the terminal block. Tightening the
     screws on the terminal block using the tightening torque of the range of 1.2 N.m.
5) Do not connect anything to unused terminals. 
   

Maintenance

1) The equipment should be cleaned regularly to avoid blockage of ventilating parts.         

2) Clean the equipment with a clean soft cloth. Do not use isopropyl alcohol or any other cleaning agent.
3) Fusible resistor must not be replaced by operator. 

www.multispanindia.com

Page-4

AVF-19N

Summary of Contents for AVF-19N

Page 1: ...ontrol Instruments Pvt Ltd 72 B Phase 1 GIDC Estate Vatva Ahmedabad 382445 Gujarat India 91 79 40029250 91 9978991471 AVF 19N 3 PHASE PANEL METER www multispanindia com marketing multispanindia com www multispanindia com AVF 19N ...

Page 2: ... III Protection Level As per request IP 65 Front side As per IS IEC 60529 2001 Technical Specification To save changes power off the Instrument Press Scroll Key for 5 seconds with power on the instrument RY YB BR A Hz V AVF 19N 3 p h 3 w C o n RY YB BR A Hz V AVF 19N C o n 1 p h 2 w Press key release to select connection type from 3P 4W 3P 3W 1P 2W WIRING CONNECTION MODE RY YB BR A Hz V L1 L2 L3 C...

Page 3: ...e 2 Line 3 Line 1 Vrn Ir Freq www multispanindia com Page 2 AVF 19N CT SELECTION PROCEDURE Press key and power on unit to set CT ratio On immediately releasing key unit allows to edit CT ratio On setting more than 975 Amp KA Led will be ON Power ON Release key to enter CT Ratio Mode CT Ratio changed by key CT RATIO MODE To save changes turn OFF the instrument If CT primary is greater than 975 Amp ...

Page 4: ...release Run mode selection RY YB BR A Hz V AVF 19N 4 1 5 5 0 0 4 9 9 RY YB BR A Hz V AVF 19N 4 1 5 4 1 5 4 1 5 RY YB BR A Hz V 415 415 415 AVF 19N RY YB BR A Hz V L1 L1 L2 L2 L3 L3 415 500 499 AVF 19N 1 2 3 4 7 8 9 12 13 14 10 11 5 6 S1 S1 S1 S2 S2 S2 L1 L2 L3 VL1 VL2 VL3 N 100 250V AC 50 60 Hz 3VA L N 3Ø 4W 3Ø 3W Accuracy Class 1 0 Range System Current 0 5 To 5A AC CAT III Voltage L L 50 500VAC C...

Page 5: ...on and internal wiring 2 Do not allow pieces of metal wire clippings or fine metallic fillings from installation to enter the product or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator 3 Circuit breaker or mains switch must be installed between power source and supply terminal to facilitate power ON or OFF function However this mains swi...

Page 6: ...www multispanindia com Page 5 AVF 19N MODEL A 96mm 96mm 92mm 92mm 3mm 50mm 53mm B C D E F G DIMENSIONS Mechanical Dimensions F D E A B Right Side View Top View G B ...

Page 7: ...Note www multispanindia com Page 6 AVF 19N ...

Page 8: ...ote Product improvement and upgrade is a constant procedure So for more updated operating information and Support Please contact our Email service multispanindia com www multispanindia com Page 7 AVF 19N ...

Reviews: