page 40 — dca220sscu/4i 60 hz generaTor • operaTion and parTs manual — rev. #0 (10/25/12)
MaiNteNaNCe
emission conTrol
The emission control system employed with the Cummins
QSB&-G6 diesel engine consist of a Diesel Oxidation
Catalyst (DOC) and a Diesel Particulate Filter (DPF). The
oxidation catalyst and particulate filter are housed in one
unit. See Figure 61.
These devices help in filtering out large amounts of harmful
Nitrogen Oxides (NOx) and Particulate Matter (PM) which
are emitted by diesel engines. These exhaust emissions
pose serious environmental and health risks. It is important
to maintain and service this DOC/DPF emission safety
device on a periodic basis.
diesel oxidation catalyst (doc)
The DOC does not filter particles it oxidizes them. This
catalyst (honeycomb like structure) uses a chemical
process to break down pollutants in the exhaust stream
into less harmful components. In general this catalyst
collects/burns accumulated particulates. The DOC contains
palladium and platinum which serve as a catalysts to oxidize
hydrocarbons and carbon monoxide.
diesel particulate Filter (dpF)
A diesel particulate filter (DPF) is a device designed to
remove diesel particulate matter (soot) from the exhaust
gas of a diesel engine. This type of filter usually removes
about 85-95% of the soot.
Soot accumulated in the DPF is removed via the
"regeneration process". Regeneration is the process
of removing the accumulated soot from the filter. This
regeneration process can occur in a few different ways.
passive regeneration
— Occurs during normal
operation, typically under heavy load applications. Soot
is oxidized faster than it is collected.
active regeneration
— Occurs when engine exhaust
temperatures are not high enough to oxidize the soot
collected in the DPF. Active regeneration requires
assistance from the engine to help increase the heat
level in the after-treatment system.
Active regeneration occurs at a normal engine speed
of 1800 rpm. In addition active regeneration is initiated
automatically by the Engine Control Module (ECM) timer
based program every 96 hours. This timer base program
will reset at the end of any regeneration mode.
Forced (stationary) regeneration
— A forced
regeneration only occurs when the operator has initiated
this action at the ECU and the ECM recognizes a pre-
programmed set point of soot in the PDF to allow a forced
regeneration cycle.
This process can take anywhere from 30 minutes to
1-1/2 hours. When forced regeneration is in process all
loads must be removed from the generator, all circuit
breakers must be placed in the OFF position (OPEN),
and the engine speed set to idle.
dpF pre-alarm
In the event the Engine Control Unit (ECU) determines
the soot level back pressure and/or tempertaure has
reached a pre-determined trip point the ECU will indicate
a maintenance action is required by the operator.
This maintenance action will be shown on the LCD display
(DPF Warning Symbol) and the AMBER pre-alarm LED on
the ECU control panel will be ON (lit). See Figure 59.
Figure 59. ECU DPF Pre-Alarm
The DPF pre-alarm status symbol displayed in Figure 59
indicates the soot level buildup has exceeded a pre-
determined level and a "Forced Regeneration" action is
required.
Series 800 Controller
ECU
Engine Started
Shutdown
Pre-Alarm
Alarm
Acknowledge
Screen
Change
Program
Exit
Option
DPF STAT
NOTICE
If the
amBer
pre-alarm warning LED is ever
on
,
the operator should always take
immediate action
to
correct the problem. If the engine is allow to run under
this condition, a higher pressure differential will be
created in the DPF and will result in the
red
status
LED being
on
, causing an engine shutdown.
Summary of Contents for MQ Power Whisperwatt DCA220SSCU
Page 5: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 5 notes...
Page 51: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 51 notes...
Page 54: ...page 54 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 GENERATOR ASSY...
Page 70: ...page 70 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 battery ASSY...
Page 72: ...page 72 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 muffler ASSY...
Page 74: ...page 74 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 fuel tank ASSY...
Page 76: ...page 76 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 ENCLOSURE ASSY...
Page 89: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 89 notes...