Multipipe 22-23001 Installer Manual Download Page 1

8. Technical Specification

Model:

22-23001

Voltage:

230 V AC, +-10%, 50/60 Hz

Operating Performance:

230 V: 1,8 W

Temperature setback: 

Temperature range: 

2°C-4°C

5°C- 30°C

Span: 

+/- 0,5°C

Storage temperature:

-20°C to +60°C

Ambient temperature:

0 °C up to 45 °C

Degree of protection

:

IP 30

CE conformity according to:

Class II ( EN60730 )

Housing material

:

PC, V2

Color:  

RAL 9010 pure white 

Connection: 

Screw terminal

Weight 

90g net / 135g gross

Puls-wide-modulation: 

(PWM)

Yes

Valve protection: 

Heating and Cooling:

Cooling blocked:

Dimensions: 

Yes

Yes, automatically Change Over on  the CO terminal

Yes, with jumper

85mm*85mm*25mm

Warranty

Multipipe warrants that this product (22-23001) will be free from any 
defect in materials or workmanship, and shall perform in accordance with 
its specification, for a period of five years from the date of installation. 
Multipipe sole liability for breach of this warranty will be (at its option) to repair or 
replace the defective product.

Customer Name: ......................................................................................................................................................

Customer Address: .................................................................................................................................................

............................................................................................................................................................................................

....................................................................................... Post Code: ...........................................................................

Tel No: .................................................................... Email: .......................................................................................

Engineers Company: ..........................................................................................................................................

Tel No: ...................................................................... Email: ....................................................................................

Instalation Date: ....................................................................................................................................................

Engineers Name: ...................................................................................................................................................

Engineers Signature: ...........................................................................................................................................

6. Protection Function

7. Control Patterns

5. Thermostat Functions

NSB (Night SetBack) Function

NSB Mode depends on the NSB wired connection. 

 

0V =   NSB OFF
230V=  NSB ON

The NSB signal is activated every 1 second. When the signal is received the 
setpoint temperature will be set at 

±

2°C or 

±

4°C.

Heating and Cooling Selection

The Heating/Cooling function is determined by the CO terminal connection.

CO 0V=    Heat mode 

CO 230V=    Cool mode

Cooling Blocked function

Cooling Enabled:
Set the jumper on ON                   . The thermostat will run in normal cooling mode. 
That means that it will open/close the actuators when necessary. The LED will be 
BLUE when the cooling function is running.

Cooling Disabled:
Set the jumper on OFF                .  The actuator will be closed and the LED will 
be off.

Heat cut off at high/low temperature:

When room temperature is over 36°C or under 4°C, all heating/cooling outputs 
will be turned off.

Short cycle protection:

When Cooling Mode is enabled the minimum interval between Relay ON/OFF 
is 3 minutes.

Valve Protection:

Set the jumper on ‘ON’ to disable the function or on ‘OFF’  to enable it. Turn on the 
valve for 5 minutes every week to prevent any damage to the valve.

Sensor Malfunction:

If the temperature sensor or temperature sensor compensation is open the LED 
will flash BLUE/RED alternatively.

If CO terminal is connected and the Heating Mode is ON, the PWM function 
will be activated.

If CO terminal is disconnected and the Cooling Mode is ON the ON/OFF control 
output will be activated.

DIAL 230 V 

THERMOSTAT

Model: 22-23001

INSTALLER MANUAL

Multipipe L

td

Unit 12 Great Ha

yes Business P

ark

Low

er Burnham R

oad

Stow M

aries

Chelmsfor

d, Essex, CM3 6SQ

Sales

T: 01245 227630

E: [email protected]

.uk

Technical

T: 01245 850799

E: technical@multipipe

.co.uk

ww

w.multipipe

.co.uk

Reviews: