Screw-in Resistance Temperature Sensor
Page-10
5 Start-Up, Operation (Continued)
5.6 Pin Assignment
Connect the instrument to earth via the process connection.
The protection class specified only applies while the pressure transmitter is connected with the female
connectors that provide the corresponding ingress protection.
Ensure that the cable diameter you select fits to the cable gland of the connector. Ensure that the cable
gland of the mounted connector is positioned correctly and that the sealings are available and
undamaged. Tighten the threaded connection and check the correct position of the sealings to ensure
device protection.
Ensure no moisture can seep in at the cable outlets.
Route the cable without applying a force or turning moment to the device.
5.5 Electrical Connection
View: Plug pins of plugs (at device)
LIYCY
4 or 6x0,25 mm²
gray
M12, 4-pole
M12, 5-pole
M12, 8-pole
Super Seal, 3-pole
Deutsch DT04, 3-pole
Deutsch DT04, 4-pole
Bayonet DIN, 4-pole
Valve, 4-pole
MIL, 6-pole
Cable, 4-, 6-pole
+ OUT -
+ OUT -
+ OUT -
M12, 4-pole
1
X 3
1
2
3 1
2
3
M12, 5-pole
1
X 3
1
2
3 1
2
3
M12, 8-pole
1
X 3
1
3
8 1
3
8
Super Seal, 3-pole
1
X 3
n/a
1
2
3
Deutsch DT04, 3-pole
A
X B
n/a
A
C B
Deutsch DT04, 4-pole
1
X 3
1
2
3 1
2
3
Bayonet, 4-pole
1
X 3
1
2
3 1
2
3
Valve, 4-pole
1
X 2
1
3
2 1
3
2
MIL, 6-pole
A
X C
A
E C A
E C
Cable, n-pole
ye X wh ye gn wh ye gn wh
3-Wire DC
3-Wire AC
Pin Assignment
2-Wire
Note: X = NC (not connected/unused)
Connection Type