15
For Multi-E4/E-MU:
This menu allows you to configure the power rating and the power factor. The power rating can be configured for
energy supply or energy transfer or for both energy directions. Inputs of 0
–
50000 can be made in three measured
categories (Watt, kW and MW). Decimal points cannot be entered. The power factor can be arbitrarily set between
0.1 capacitive and 0.1 inductive. Any values outside of this range are displayed as an error message.
„Power / cos phi“ menu Multi
-E4/E-MU
“Outputs 1 –
4”
menu (only Multi-E4-MU)
This program menu allows you to configure the 4 analogue outputs. Any measured variable can be assigned to each
output but every measured variable can only be assigned to one output. Outputs 1
–
4 can be configured as unipolar
outputs (e.g. 0
–
20 mA / 0
–
10 V) or as bipolar outputs (e.g.
–
20
–
0
–
20 mA /
–
10
–
0
–
10 V). Due to the outputs
being bipolar analogue outputs, only those outputs which have actual, reactive or apparent output measured values
or a cos phi power factor can be activated. At the analog outputs are the sum values of the actual, reactive or
apparent power or cos phi power factor displayed.
„Outputs 1
-
4“ menu Multi
-E4-MU