6.3  Leak test 

 

CAUTION: The control device must not be 
included in a strength test (design review) of the 
entire installation. 

 

 

Close all shut-off valves of the connected devices. 

 

apply test pressure according to TRF 2012 

 

wait for temperature adjustment  

 

test duration 10 minutes (the pressure must not 
drop) 

 

spray all connections with foaming agents (e.g. leak 
detection spray) and check for leaks.

 

 

NOTE! 

We recommend the leak test with our testing device 
(Art. No.: 1 00 098 14 018 2). 

 

DANGER! 

 

Before each commissioning of a new installation or 
recommissioning of an installation after repairs or 
modifications, the following must be ensured: 

 

proper completion of all installation/assembly work! 

 

commissioning only by "Qualified personnel "(see 
point 2.3). 

 

passed leak test 

 

7.   Operation 

 

7.1  Initial commissioning 

 
After completion of the leak test the pressure regulator is 
ready for operation. 
 

7.2  Decommissioning 

 
If the supply and consumption system is to be taken out of 
operation, all shut-off valves must be closed and the pipe 
system drained. All open connections must be secured with a 
suitable seal. 
 

7.3  Recommissioning 

 
When recommissioning the regulator, make sure that all the 
relevant steps are repeated as described in section 6.1 to 
section 6.3. 
If recommissioning is not possible, the manufacturer must be 
informed. 
 

7.4  Maintenance 

 
If the points in section 6 are observed, the pressure regulator 
is maintenance free. 

 

8.   Cause and remedy of operating faults 

 

8.1  Fault detection 

 

DANGER! 
When troubleshooting, the hazard warnings 
under 2 must be observed. 

 

 

If the faults cannot be rectified using the following 
table "Troubleshooting (8.2)", the manufacturer must 
be consulted. 

 

In case of malfunctions of the function or the 
performance, it must be checked whether the 
installation work has been carried out and completed 
according to these operating instructions. 

 

The information on pressure, temperature, and 
direction of flow as well as the operating conditions 
must correspond to the data sheet or the technical 
data on the type plate. 

 

8.2  Troubleshooting 

 

Fault 

Measures 

Gas smell 

Caution: Fire and 

explosion hazard! 

Keep calm, close the gas supply, open 

windows and doors, do not operate 

any electrical switches, contact a 

specialist. 

 

No gas flow 

Open shut-off valves, check level 

indicator if necessary, 

OPSO is closed (see 

Recommissioning OPSO), check the 

filter in the inlet connection as well 

as the vent openings and clean if 

necessary or contact the 

manufacturer. 

 

Consumption 

appliance on fault 

After depressurising the system, 

connect the "Müller test unit" to the 

appropriate test connections on the 

regulator and take measurements: 

 

inlet pressure (upstream 

pressure before the 

controller stage) 

 

outlet pressure (idle 

pressure, consuming device 

not in operation 

 

outlet pressure (flow 

pressure, consumer unit in 

operation) 

 

connection pressure at the 

consumer unit 

Then compare the values with the 

technical data of the regulator and

 

the consumer unit. 

 
 

NOTE! 
Before carrying out assembly and repair work, 
please observe Section 10 

 

9.   Repairs 

 
In order to ensure the proper functioning of the installation 
under normal operating conditions, it is recommended to 
replace the device before 10 years have elapsed since the 
date of manufacture. 
The 10 years is a recommendation that can be replaced by 
national laws or technical regulators, taking into account the 
operating conditions of integrated safety devices and 
maintenance schedules. 
 

According to DGUV 79: 

The Contractor must ensure that parts of consumable 
equipment that are subject to wear and aging are replaced 
after a maximum of 8 years. This does not apply if the proper 
condition has been confirmed by an expert. 
 

10.   Warranty 

 
The scope and period of warranty is defined in the version of 
the "General Terms and Conditions" of Müller Gastechnik 
GmbH valid at the time of delivery. 
 
All information and notes in this manual have been compiled 
taking into account the applicable standards and regulations, 
the state of the art and our many years of expertise and 
experience. The manufacturer accepts no liability for 
damages due to: 

 

Non-compliance with the instructions 

 

Unintended use 

 

Use of untrained personnel 

 

Unauthorised conversion 

 

Technical changes 

 

Use of non-approved spare parts. The actual scope 
of delivery may differ from the explanations and 
illustrations described here in the case of special 
versions, the use of additional ordering options or 
due to the latest technical changes. 

 
 
 
 
 
 