48
Operation
3.2
Putting the engine into operation after scheduled
out-of-service-period
Preconditions
• Engine is stopped and starting disabled.
Putting the engine into operation
Item
Task
Lube oil system
Check oil level (
Cooling system
Check engine coolant level (
Check charge-air coolant level (
Cooling system
Preheat coolant with preheating unit.
Fuel prefilter
Drain (
Monitoring equipment
Carry out lamp test (see manufacturer’s documentation).
Engine/generator control system
Switch ON;
Select operating mode, e.g. MANUAL OPERATION,
AUTOMATIC OPERATION.
M015715/00E 06-08