MTT MS3720 User Manual Download Page 2

  User's Manual 

MS3720 

Slim Plug-In CT Transmitter with Isolated Single/Dual Output 

 

Rev. 1.90 

 
 

 

 
On Wiring: 

  Connections to the instrument should be made to the terminal 

block. For assignment of the terminals, refer to section 6. The 
recommended screwing torque is 0.8 to 1.0 Nm. 

  For lead wires, use a highly flexible stranded conductor. The 

recommended nominal cross-section of the lead wire conductor 
is 0.5 to 2.0 mm

2

. Additionally, the conductor for input lines 

should have a cross-section of at least 2.0 mm

2

  The connection of the lead wire to the terminal block should be 

made with the insulated crimp terminal attached to the end of the 
wire. Without the insulation, short circuit or electric shock may 
occur. The recommended thickness of the crimp terminal is 0.7 
to 1.0 mm. 
Note that only up to two (2) crimp terminals can be connected to 
one (1) terminal screw. In this case, the thickness of the crimp 
terminal should be not greater than 0.8 mm. (As for the input 
terminals, only one crimp terminal should be connected.) 
It is recommended that ring crimp terminals be used for input 
wiring to prevent them from easily coming off.

 

 

φ3.7

6.8

 m

ax

.

3.4 max.

4.6 min.

 

 

To Avoid Erroneous Measurements: 

  In order to reduce the influence of noise, the input/output wire 

and power supply wire should not be used in a same bundle or 
same conduit. They should be installed separately with a 
minimum distance of 200 mm. 

 Avoid wiring the signal lines in the vicinity of equipment 

generating magnetic fields or electromagnetic waves, such as 
electric motors and large-scale transformers. If inevitable, 
anti-noise measures such as employment of shielded wires are 
indispensable. 

  At least 30 minutes of warm-up is required prior to operation. 

  Any sensor or equipment to be connected to the instrument 

should be selected in consideration of the input/output 
impedance of the same. (For detailed specifications, refer to 
section 4 or the relevant product specification sheet that can be 
downloaded from our website at https://www.mtt.co.jp.) 

 

On Shunt Resistor: 

  Check that the package contains a shunt resistor. 

  Before using the instrument, connect the shunt resistor across 

the terminals specified below. If the instrument is used without 
the shunt resistor, the secondary circuit of the CT will be opened, 
which may cause the CT to burn out. 
The shunt resistor supplied is not interchangeable. Be sure to 
check that the serial numbers of the shunt resistor and the unit 
are exactly the same. 

 

Shunt Resistor

 

 

Special Notes for CE Marking:

 

  The instrument is designed and manufactured to conform to the 

following EMC and Low Voltage Directives: 
EMC Directive (2014/30/EU) 
    - Standard conformity: EN61326-1:2013 Class A 
Low Voltage Directive (2014/35/EU) 
    - Standard conformity: IEC61010-1 
                                            EN61010-1:2010/A1:2019 
    - Overvoltage Category: II 
    - Pollution Degree: 2 

  The instrument must be installed in a control panel. 

  The instrument maintains basic insulation between input and 

output, and between output and FG. Prior to installation, check 
that the insulation class of the instrument satisfies your system 
requirements. 

  When the instrument is installed in a control panel, the measures 

to be taken for CE marking conformity may vary with the type of 
devices connected, wiring to the instrument or structure of the 
control panel. Therefore, you should check that the control panel 
as an overall system conforms to the CE marking regulations. 

 

4. About the Product

 

The MS3720 accepts AC input from CT and provides isolated DC 
output.

 

 

Features: 

  Pin and socket contacts are gold-plated (0.2

μ

m) to ensure high 

reliability and long-term stability. 

  High dielectric strength of 2,000 VAC between input, [output 1, 

output 2], power, and ground. 

  The power unit can deliver AC power ranging from 85 to 264V 

steplessly without switching to meet varied power requirements. 

  Plug-in type for better maintainability 

  Drop-proof terminal screws for ease and safety of installation 

  Fuse installed in the power line as standard. 

 