User's Manual
MS3708
Slim Plug-In Frequency/Analog Converter with Isolated Single/Dual Output
Rev. 1.40
2
On Wiring:
Connections to the instrument should be made to the terminal
block. For assignment of the terminals, refer to section 6. The
recommended screwing torque is 0.8 to 1.0 Nm.
For lead wires, use a highly flexible stranded conductor. The
recommended nominal cross-section of the lead wire conductor
is 0.5 to 2.0 mm
2
.
The connection of the lead wire to the terminal block should be
made with the insulated crimp terminal attached to the end of the
wire. Without the insulation, short circuit or electric shock may
occur. The recommended thickness of the crimp terminal is 0.7
to 1.0 mm.
Note that only up to two (2) crimp terminals can be connected to
one (1) terminal screw. In this case, the thickness of the crimp
terminal should be not greater than 0.8 mm.
φ3.7
6.8
m
ax
.
3.4 max.
4.6 min.
To Avoid Erroneous Measurements:
In order to reduce the influence of noise, the input/output wire
and power supply wire should not be used in a same bundle or
same conduit. They should be installed separately with a
minimum distance of 200 mm.
Avoid wiring the signal lines in the vicinity of equipment
generating magnetic fields or electromagnetic waves, such as
electric motors and large-scale transformers. If inevitable,
anti-noise measures such as employment of shielded wires are
indispensable.
At least 30 minutes of warm-up is required prior to operation.
Any sensor or equipment to be connected to the instrument
should be selected in consideration of the input/output
impedance of the same. (For detailed specifications, refer to
section 4 or the relevant product specification sheet that can be
downloaded from our website at https://www.mtt.co.jp.)
4. About the Product
The MS3708 converts pulse train signals into isolated DC signals.
Features:
Pin and socket contacts are gold-plated (0.2
μ
m) to ensure high
reliability and long-term stability.
High dielectric strength of 2,000 VAC between input, [output 1,
output 2], power, and ground.
The power unit can deliver AC power ranging from 85 to 264V
steplessly without switching to meet varied power requirements.
Plug-in type for better maintainability
Drop-proof terminal screws for ease and safety of installation
Fuse installed in the power line as standard.
Specifications
Input Resistance
Voltage input: 1M
Ω
min. with power
30k
Ω
min. without power
Current input: 250
Ω
(standard for 4-20mA)
Allowable Input
Voltage
DC voltage input: 30V DC max., continuous.
DC current input: 40mA DC max., continuous.
AC voltage input: 200Vp-p AC max.,
continuous (up to ±100V with reference to 0V).
Input Pulse
Width
4µs min.
Duty Ratio
40 to 60%
Allowable Output
Load
Voltage output:
1V span and up: 2mA max.
10mV: 10k
Ω
min.
100mV: 100k
Ω
min.
Current output:
Single current output:
750
Ω
max. (for 4-20mA output)
Dual current output:
Output 1: 550
Ω
max. (for 4-20mA output)
Output 2: 350
Ω
max. (for 4-20mA output)
Zero Adjustment
Approx. ±5% of span.
(Adjustable by the front-accessible trimmer.)
Span Adjustment
Approx. ±5% of span.
(Adjustable by the front-accessible trimmer.)
Accuracy Rating
Better than ±0.3% of span
Ripple: 0.2%p-p or less of span (for at least
10% input) (at 25°C±5°C)
Temperature
Effect
Better than ±0.2% of span per 10°C change in
ambient.
Response Time
Input Frequency
0-90% with a step input
at 100%
20Hz 8s
max.
200Hz 1s
max.
2kHz 500ms
max.
20kHz 500ms
max.
Insulation
Resistance
100M
Ω
min. (@ 500V DC) between input,
output 1, output 2, power, and ground.
Dielectric
Strength
Input / [Output 1, Output 2] / [Power, Ground]:
2000V AC for 1 minute (Cutoff current: 0.5mA)
Power / Ground: 2000V AC for 1 minute (Cutoff
current: 5mA)
Output 1 / Output 2: 500V AC for 1 minute
(Cutoff current: 0.5mA)
Surge Withstand
Capability
Tested as per ANSI/IEEE C37.90.1-1989.
Storage
Temperature
-10 to 60°C
Installation Position
Typical Installation Example