MTT MS3705HA User Manual Download Page 2

  User's Manual 

MS3705HA  Slim Plug-In Digital Alarm Setter with Isolated Dual Output (High Accuracy Model) 

 

Rev. 1.60 

 
 

 

 
On Wiring: 

  Connections to the instrument should be made to the terminal 

block. For assignment of the terminals, refer to section 6. The 
recommended screwing torque is 0.8 to 1.0 Nm. 

  For lead wires, use a highly flexible stranded conductor. The 

recommended nominal cross-section of the lead wire conductor 
is 0.5 to 2.0 mm

2

  The connection of the lead wire to the terminal block should be 

made with the insulated crimp terminal attached to the end of the 
wire. Without the insulation, short circuit or electric shock may 
occur. The recommended thickness of the crimp terminal is 0.7 
to 1.0 mm. 
Note that only up to two (2) crimp terminals can be connected to 
one (1) terminal screw. In this case, the thickness of the crimp 
terminal should be not greater than 0.8 mm.

 

 

φ3.7

6.8

 m

ax

.

3.4 max.

4.6 min.

 

 

To Avoid Erroneous Measurements: 

  In order to reduce the influence of noise, the input/output wire 

and power supply wire should not be used in a same bundle or 
same conduit. They should be installed separately with a 
minimum distance of 200 mm. 

 Avoid wiring the signal lines in the vicinity of equipment 

generating magnetic fields or electromagnetic waves, such as 
electric motors and large-scale transformers. If inevitable, 
anti-noise measures such as employment of shielded wires are 
indispensable. 

  At least 30 minutes of warm-up is required prior to operation. 

  Any sensor or equipment to be connected to the instrument 

should be selected in consideration of the input/output 
impedance of the same. (For detailed specifications, refer to 
section 4 or the relevant product specification sheet that can be 
downloaded from our website at https://www.mtt.co.jp.) 

 

4. About the Product

 

The MS3705HA compares the levels of DC current or voltage 
signals with two set-points selected using front panel switches and 
outputs two independent isolated relay contact closure signals.

 

 

Features: 

  Manual setting by front panel switches, enabling any set-point 

within the range of 0 to 105% (in 0.1% steps; but in 1% steps for 
the range over 100%). 

  Relay activation mode and hysteresis settings are possible with 

the front panel switches. 

  Pin and socket contacts are gold-plated (0.2

μ

m) to ensure high 

reliability and long-term stability. 

  High dielectric strength of 2,000 VAC between input, [output 1, 

output 2], power, and ground. 

  The power unit can deliver AC power ranging from 85 to 264V 

steplessly without switching to meet varied power requirements. 

  Plug-in type for better maintainability 

  Drop-proof terminal screws for ease and safety of installation 

  Fuse installed in the power line as standard. 

 

Specifications 

 

Input Resistance 

Voltage input: 

1M

Ω

 min. with or without power. 

 

Current input: 250

 (Standard for 4-20mA DC)   

Allowable Input 
Voltage 

Voltage input: 30V DC max., continuous. 
(Standard for a span up to 10V) 

 

Current input: 40mA DC max., continuous. 
(Standard for 4-20mA) 

 

Output 

Two independent form C relay contact closure 
signals 

 

Trip Points 

Setting: Through the front-accessible setting 
switches. 
Range: 0 to 105% of span (in 0.1% steps; but 
in 1% steps for the range over 100%) 
Accuracy: Better than ±0.1% of span 
Hysteresis: 0.5 to 50%±0.1% of span 
Note: The upper and lower hysteresis limits are 
respectively 110% and -10% of span. 

 

Relay Status 
Indicator LED 

Red LED lights up when the relay is activated.   

Relay Activation 
without Power 

COM and NC are closed for each output. 

 

Relay Start-up 
Limitation 

The relay gets ready for action 2 seconds after 
power-up. 

 

Temperature 
Effect 

Better than ±0.15% of span per 10°C change in 
ambient. 

 

Response Time  150ms max. (0-90%) with a step input at 100%.  
Insulation 
Resistance 

100M

Ω

 min. (@ 500V DC) between input, 

output 1, output 2, power, and ground. 

 

Dielectric 
Strength 

Input / Output 1 / Output 2 / [Power, Ground]: 
2000V AC for 1 minute (Cutoff current: 0.5mA) 
Power / Ground: 2000V AC for 1 minute (Cutoff 
current: 5mA) 

 

Relay Contacts 

Rated load: 5A 125VAC, 5A 30VDC 
Maximum allowable voltage: 250VAC, 30VDC 
Maximum allowable current: 5A (NO) / 3A (NC) 
Electrical life: 

5A 250VAC (NO): 50×10

3

 cycles 

(Frequency: 1,800 cycles/h) 
5A 30VDC (NO): 100×10

3

 cycles 

(Frequency: 1,800 cycles/h) 

Mechanical life: 

5×10

6

 cycles (Frequency: 18,000 cycles/h) 

 

Surge Withstand 
Capability 

Tested as per ANSI/IEEE C37.90.1-1989. 

 

Storage 
Temperature 

-10 to 60°C 

 

Installation Position

 

Typical Installation Example

 