10. Adjustment

 

Since the unit is precisely factory-adjusted before shipment, no 
further adjustment is needed at the user’s side. Adjustment of signal 
conditioners requires technical expertise and fine craftsmanship. We 
recommend that you use adjustment service of MTT to save costs 
and ensure accuracy. Please contact MTT or its local 
representatives. Just for your reference, the adjustment procedure 
is described below.

 

10-1. Preparation

 

  For the terminal assignments, refer to section 5. 

  The wiring work should be performed with no power applied to 

the instrument. 

  Wiring should be connected to the terminal block. 

  At least 30 minutes of warm-up is required before adjustment. 

  The accuracy of measuring equipment to be used for calibration 

must be much higher than that of the instrument to be adjusted. 

  Since the ZERO and SPAN Trimmers work on both the output 1 

and output 2, adjustment should be performed on the output 1. 
(Adjustment of the output 1 has the same effect on the output 2.) 

10-2. Adjustment Procedure 

(1)  Connect the unit as illustrated below. 
(2)  Adjust the resistance source to generate a signal equivalent to 

0%* of the input range of the unit. 

(3)  Slowly turn the ZERO Trimmer to get 0%* output while applying 

0%* input as above. 

(4)  Adjust the resistance source to generate a signal equivalent to 

100% of the input range of the unit. 

(5) Slowly turn the SPAN Trimmer to get 100% output while 

applying 100% input as above. 

(6)  Repeat steps (2) through (5) until zero and span are precisely 

adjusted. 

(7)  Adjust the resistance source to generate 25%, 50% and 75% of 

the input signal range of the unit and record the values of output 
signals to confirm they are linearly proportional. 

* For 0 to 20mA output, 0% should be interpreted as 0.5%. 
 

CALIBRATED
ADJUSTABLE
RESISTANCE
SOURCE

MULTIMETER

POWER SUPPLY

 

 
 

11. Maintenance and Inspection

 

Check the unit for proper characteristics and settings about once 
every two years. 

 

12. Warranty Period and Scope

 

[Warranty Period]

 

MTT’s hardware products are warranted for a period of seven (7) 
years from the date of shipment.

 

[Warranty Scope]

 

1)  MTT warrants that its hardware products are free from defects 

in materials and workmanship and conform to its product 
specifications. 

2) MTT ships the products under its appropriate quality 

management system and quality control, but does not warrant, 
expressed or implied, that the operation, output, or indication 
of the hardware will be uninterrupted or error free. MTT shall 
not be liable and make no warranty for any damage to or any 
safety or performance trouble in the customer’s or any other 
third party’s equipment if the operation, output, or indication is 
interrupted or faulty. 

3) If, during the warranty period, the product proves to be 

defective when used in accordance with the relevant user’s 
manual, the product will be repaired or replaced. 

4)  This warranty does not apply to any malfunction or failure 

resulting from the following: 
a.  Improper or incomplete maintenance or calibration, 
b.  Any other cause, which does not relate with the delivered 

product, 

c.  Modification or repair by any person other than MTT, and 
d.  Natural disasters or other unavoidable accidents, for which 

MTT is not liable. 

 
 
 
 

 

Summary of Contents for MS3702B

Page 1: ...tch below namely in such a position that the label on the front panel is readable in the right direction For effective heat dissipation allow a space of at least 100 mm above and below the unit When units are used in multiple stacks they should be spaced at least 130 mm apart from each other If the required minimum space is not available take appropriate heat protection measures by e g placing a p...

Page 2: ...t can be downloaded from our website at https www mtt co jp 4 About the Product The MS3702B accepts RTD input and provides isolated DC output Features The unit includes linearization and burnout protection Pin and socket contacts are gold plated 0 2μm to ensure high reliability and long term stability High dielectric strength of 2 000 VAC between input output 1 output 2 power and ground The power ...

Page 3: ...inish the tightening 9 Mounting Demounting Mounting the Socket on a DIN rail Demounting the Socket Main Unit Installation Removal Fixing Screw I O Pins Installation 1 Identify the top and the bottom of the unit and insert the I O pins straight into the corresponding pin slots receptacles on the socket 2 Tighten the fixing screw to fix the unit firmly in position Removal 1 Loosen the fixing screw 2...

Page 4: ...peat steps 2 through 5 until zero and span are precisely adjusted 7 Adjust the resistance source to generate 25 50 and 75 of the input signal range of the unit and record the values of output signals to confirm they are linearly proportional For 0 to 20mA output 0 should be interpreted as 0 5 CALIBRATED ADJUSTABLE RESISTANCE SOURCE MULTIMETER POWER SUPPLY 11 Maintenance and Inspection Check the un...

Reviews: