MTHPUMPS T31 SERIES Manual Download Page 6

Page 506

Connect the vacuum line to the dis-

charge side of the pump, either in the 

discharge opening or the drain tap. A 

foot valve is not necessary when this 

kind of device is used.

When a vacuum pump is not practical, 

a foot valve in the suction inlet can be 

used to prevent liquid from running out. 

The pump and suction line can then be 

filled completely from an outside source. 

A vent opening will be necessary during 

filling to let air escape. A tight foot valve 

will keep the pump constantly primed so 

that automatic operation is possible. The 

valve should be inspected regularly to 

see that it does not develop leaks which 

would allow the pump to run dry.

Optional self-priming casings are avail-

able for MTH pumps allowing priming 

when a vacuum pump or foot valve is 

not practical. Refer to specific literature 

for details. 

There are four components to the self 

primer:

1.  A check valve - necessary to main-

tain a vacuum in the suction line as 

surging occurs in the pump.

2.  An air eliminator - used on the dis-

charge side of the pump to separate 

air from liquid so the liquid can be 

used again as air is carried through 

the pump.

3.  A recirculating line - carries liquid 

from the air eliminator to the suction.

4.  A fluid chamber - used on the inlet 

side to provide a supply of fluid to 

speed up priming.

Small suction lines are desirable to 

minimize priming time. 

Using the self priming casing, it is only 

necessary to: 

1.  Open the plugs in both the inlet and 

discharge chambers. 

2.  Pour fluid in one until both are full.

3.  Tighten both plugs.

4.  Turn on the pump.

Priming time depends on lift, volume of 

air in the suction line, and the size of 

the regenerative turbine pump used. If 

priming time is long and the pump be-

comes warm, refill the priming chambers 

with fresh liquid. Most turbine pumps will 

pump twenty-six to twenty-eight inches 

of mercury vacuum with cold water in 

the pump, but have very little capacity 

and therefore are not practical at lifts 

over twenty-two feet.

The best way to prime a pump and keep 

it primed is to use a flooded suction. 

While this is not always practical, it does 

provide a number of advantages. The 

likelihood of pump damage from dry run-

ning is eliminated. Suction lines may be 

large, reducing line losses and minimiz-

ing the potential of cavitation damage. 

There are no check valves or priming 

devices to fail or require maintenance. 

Whenever possible, design pumping 

systems with flooded suction.

3H Starting

Before starting a pump for the first time, 

be sure that all the preceding operations 

have been carried out. Proper rotation, 

priming, and a free turning pump are 

most important. 

1.  Start the pump with the minimum 

possible line restriction.

2.  Open discharge valves before press-

ing the starter. 

3.  Start the pump and let the system 

clear of air.

4.  Listen for foreign material being car-

ried through the pump.

5.  Slowly close necessary valves or oth-

erwise place the pump into service.

6.  Listen for indications of undue load or 

other sounds indicating problems.

7.  Use a clip-on ammeter to check for 

a steady load after approximately 

fifteen minutes of operation.

3I Stopping

It is best to stop the pump with the 

least discharge head possible both for 

minimizing strain on components and to 

be in low power mode in anticipation of 

T31 SERIES

4.

Maintenance

CLOSE COUPLED PUMPS

A.

 Seals

B.

 Cooling Water

C.

 Lubrication

4A Seals

Mechanical seals are used in MTH 

Pumps to eliminate the maintenance 

that is normally associated with packing 

boxes. This does not, however, mean 

they can totally be ignored. Check a new 

installation for seal leakage.

Maintenance of seals consists primarily 

of periodic observation, looking for the 

first signs of failure. An occasional drip 

that continues to worsen is an indica-

tion that the seal has failed and must be 

replaced. Follow the appropriate disas-

sembly/assembly instructions. Always 

shut down a pump with failed seals 

as soon as possible. Leaky seals are 

usually followed by bearing failures and 

then possible pump damage as rotating 

parts become mis-aligned.

4B Cooling Water

If a heat exchanger is used to supply 

cooling water for the seals, check the 

Figure 4-2 Standard Seal Consrtuction

Figure 4-1

Seat

"O" Ring

Washer

Fexible 

Diaphragm

Retainer

Drive Ring

Spring

Spring 

Holder

restarting. If the pump will be down for 

more than a few weeks it is advisable to 

drain it. Follow the instructions for long 

term storage, Section 1, 1B Storage. 

After any prolonged stoppage, turn the 

pump over by hand before restarting, to 

be sure it is free.

Summary of Contents for T31 SERIES

Page 1: ...Manual HORIZONTAL CLOSE COUPLED FLEXIBLE COUPLED Distributed in the UK by Pump Engineering Limited Unit B1 Riverside Industrial Estate Littlehampton West Sussex BN17 5DF United Kingdom Tel 01903 7309...

Page 2: ...turer s instructions for connecting the motor Note the correct rotation and wiring diagrams on the assembly Make sure the motor rotation and speed matches that required for the pump When making electr...

Page 3: ...components required for servicing plus bearings shaft and drive keys for flexible coupled pumps should be obtained A factory rebuild should be considered whenever your disassembly indicates rebuildin...

Page 4: ...ing Other means such as pipe hangers and pipe supports should be used to carry piping to avoid misalignment and distortion Consideration should be given to thermally induced expansion and contraction...

Page 5: ...turn over by hand after they have been allowed to dry out inside New pumps from the factory are tested using rust inhibitors to preclude this possibility On site system flushing may remove these inhi...

Page 6: ...age from dry run ning is eliminated Suction lines may be large reducing line losses and minimiz ing the potential of cavitation damage There are no check valves or priming devices to fail or require m...

Page 7: ...et face down on a clean flat surface Look into the opening in the center of the motor bracket and you will see a portion of the seat Insert the 11 16 dowel and very gently tap the seat until it drops...

Page 8: ...Place the large O ring 7 into the outside O ring groove in the motor bracket Place the two 2 smaller O rings 8 into the smaller O ring grooves 9 Place the cover 2 over the motor bracket and install t...

Page 9: ...have occurred during disassembly Re clean parts as necessary 5D Reassembly All parts should be visually inspected and cleaned or replaced as outlined in 5C above It is recommended that the bearings b...

Page 10: ...strainer or foot valve too small or clogged Inspect and clean out as necessary Fittings and lines should be at least equal to the pump suction size 8 Discharge head too high Install a pressure gauge...

Page 11: ...a few weeks the noise level will diminish and will be noticeably quieter as it approaches a run in condition 6G Mechanical Problems 1 Short bearing life Bearings damaged due to leaky seals Coupling m...

Page 12: ...that a Product has failed to meet its Operational Specifications the Purchaser must request a Return Goods Authorization RGA in the manner specified at http www mthpumps com and supply any additional...

Reviews: