MTH PUMPS D91 SERIES Manual Download Page 2

UNIT INSPECTION 

Inspect the unit for damage. Report 

any damage to freight carrier im-

mediately. Check motor nameplate to 

make sure voltage and phase match 

the available power supply. 

INSTALLATION 

Locate the pump as close to the 

liquid source as possible. Protect 

the pump from freezing. The pump 

should be located at a low point to 

keep the impeller submerged at all 

times. Always leave room around the 

pump for servicing and ventilation. 

Units may be installed horizon-

tally, inclined, or vertically. All piping 

should be independently supported 

and never forced into fi tting, this will 

cause undue stress and could cause 

binding within the pump.

SUCTION PIPING 

Always use pipe that is the same size 

or one size larger than the suction 

size of the pump. NEVER use pipe 

smaller than the pump suction size. 

The D91EF has a 2” NPT suction and 

we recommend a section of pipe 20 

inches long as the lead suction pipe. 

See Typical Piping Diagram fi gure 

1-1. This allows for a smooth even 

entry of liquid into the impeller. We 

also suggest installing a gate valve 

and a union so the pump can easily 

be isolated for servicing. 

CAUTION -Never use the suction iso-

lation valve to throttle the pump. 

Make sure all joints are tight. Avoid 

air pockets. If an eccentric pipe 

reducer is used, make sure it is 

installed straight side up. Air in the 

suction line can cause the pump to 

cavitate. Always make sure suction 

pipe and fi ttings are independently 

supported. NEVER use the pump to 

act as pipe support, this could make 

the pump bind or break. 

DISCHARGE PIPING 

Always use pipe that is the same 

size or one size larger than the 

discharge size of the pump. If you 

use pipe smaller than the 1 1/2” 

NPT discharge on the D91EF, the 

pumping capacity will be diminished. 

We recommend a section of pipe 15 

inches long as the lead pipe out of 

the pump discharge. A check valve, 

gate valve and a union should also 

be installed in the discharge line for 

pump throttling and servicing. See 

Typical Piping Diagram fi gure 1-1. 

Make sure the discharge line is well 

supported. NEVER use the pump as 

pipe support. 

ELECTRICAL CONSIDERATIONS 

Electrical supply must be a separate 

branch circuit with fuses or circuit 

breakers. Install a disconnect switch 

as close to the pump as possible. 

Wire in accordance with the National 

Electric Code and local codes where 

applicable. 

CAUTION -Always disconnect electri-

cal power when handling the pump or 

controls. 

Motors must be wired for proper 

voltage. Motor wiring diagram is on 

the motor nameplate. Single-phase 

motors are usually furnished as dual 

voltage 115/230/1/60. Three phase 

motors are usually furnished as tri 

voltage 208/230/460/3/60. All three 

phase motors require a magnetic 

motor starter and thermal overload 

protection. Single-phase motors up 

to and including 1 horsepower have 

built in thermal protection. Check 

motor nameplate to confi rm overload 

protection is built in. All single-phase 

motors above 1 HP require magnetic 

starters and thermal overload protec-

tors. Always limit your wire size so 

the maximum voltage is no more than 

10% of motor nameplate voltage at 

the motor leads. If this voltage drop 

is exceeded, motor and pump life will 

be greatly diminished. 

MOTOR ROTATION 

The correct motor rotation (when 

viewed from the motor end of the 

pump) is clockwise. Pop cap off the 

back of the motor; the motor shaft is 

now exposed for viewing. Switch the 

power on and off quickly and observe 

the motor shaft. If the rotation is 

counterclockwise change any two 

motor leads on a three-phase motor. 

Single-phase motors are nonrevers-

ible.

PUMP STARTUP 

Make sure the suction gate valve 

is wide open; when the pump is in 

operation this valve should never be 

throttled. Open the discharge gate 

valve about 1/4 open. This will prime 

the pump and force air out. NEVER

Figure 1-1

Reviews: