MTE SineWave Guardian Installation Manual Download Page 14

High Frequency SineWave Guardian Installation Guide 380V-480V

 

Form: SHF-IG-E January 2018 Rev 002                    mtecorp.com                                            14 

Sequence of Operation 

1.  Read and follow safety precautions. 
2.  After installation, ensure that: 

  All filter ground terminals are connected to ground. 

  Power wiring to the utility, drive, filter, capacitor panels and motor is in accordance 

with the power wiring connection diagrams shown in installation instructions 
section. 

3.  Check that moisture has not condensed on the filter components. If moisture is present, 

do not proceed with startup until the moisture has been removed. 

4.  Disconnect filter output terminals from the motor. 
5.  Set the drive switching frequency between 4.8 kHz and 8 kHz. Refer to the drive user 

manual. 

6.  Connect filter temperature safety overload switch into the control circuit so that the drive 

will shut down in an overload situation. 

7.  Confirm that drive voltage is present at the input terminals (U1, V1, W1) of the filter. 
8.  Confirm that drive voltage is present at the output terminals (U2, V2, W2) of the filter. 
9.  Connect the filter output to the motor. 
10. Refer to the drive user manual for the drive startup procedure. Observe all safety 

instructions in the drive user manual. 

 

 

Summary of Contents for SineWave Guardian

Page 1: ...ION GUIDE FORM SHF IG E REL January 2018 REV 002 2018 MTE Corporation WARNING High Voltage Only a qualified electrician can carry out the electrical installation of this filter Quick Reference How to...

Page 2: ...ROUNDING 7 POWER WIRING CONNECTION 8 BASIC SCHEMATIC DIAGRAM 9 OPEN PANEL UNIT INTERCONNECTION DIAGRAM 10 ISOLATION TRANSFORMER DIAGRAM 11 TORQUE RATINGS 12 4 START UP 13 STARTUP CHECKLIST 13 5 TROUBL...

Page 3: ...l injuries or even death Caution Caution describes situations that can lead to malfunction or possible equipment damage WARNING High Voltage Warning warns of situations that dangerously high voltage i...

Page 4: ...Injury or death may result if safety precautions are not observed The filter must be grounded with a grounding conductor connected to all grounding terminals Open panel filters must have reactor grou...

Page 5: ...er The High Frequency SineWave Guardian Motor Protection Filter has been subjected to demanding factory tests before shipment Carefully inspect the shipping container for damage that may have occurred...

Page 6: ...chanical configuration Modular Modular units consist of a reactor and one or more capacitor panel assemblies referred to as cap panels on drawings and diagrams Additional wiring between the reactor an...

Page 7: ...o be aware of minimum electrical clearances as defined by the appropriate system safety standard s These filters generate heat and should be positioned away from heat sensitive components Avoid locati...

Page 8: ...and capacitor assemblies are shown in Table 3 2 p12 Refer to the drive user manual for instructions on interconnecting the drive and motor and the correct start up procedures for the drive The filter...

Page 9: ...High Frequency SineWave Guardian Installation Guide 380V 480V 9 mtecorp com Form SHF IG E January 2018 Rev 002 Basic Schematic Diagram Figure 3 1 Basic Schematic Diagram...

Page 10: ...High Frequency SineWave Guardian Installation Guide 380V 480V Form SHF IG E January 2018 Rev 002 mtecorp com 10 Open Panel Unit Interconnection Diagram Figure 3 2 Open Panel Interconnection...

Page 11: ...High Frequency SineWave Guardian Installation Guide 380V 480V 11 mtecorp com Form SHF IG E January 2018 Rev 002 Isolation Transformer Diagram Figure 3 3 Isolation Transformer...

Page 12: ...2x or 1 0 N A N A CAPPANEL 003 4 60 250 1 2x or 250K CMIL N A N A CAPPANEL 002 4 60 305 2 0 2x N A N A CAPPANEL 002 3 60 415 4 0 2x N A N A CAPPANEL 002 2X 4 each 60 515 300 MCM 2x N A N A CAPPANEL 00...

Page 13: ...ng internal components Connect a DC voltmeter across the capacitor terminals and ensure that the voltage is at a safe level Use extreme caution to avoid contact with line voltage when checking for pow...

Page 14: ...sture is present do not proceed with startup until the moisture has been removed 4 Disconnect filter output terminals from the motor 5 Set the drive switching frequency between 4 8 kHz and 8 kHz Refer...

Page 15: ...across the capacitor terminals or terminals U1 V1or V1 W1 and ensure that the voltage is at a safe level To aid in troubleshooting two interconnection diagrams and a troubleshooting guide that lists...

Page 16: ...ed motor rating Solution Verify the filter is properly sized for the application Possible cause Capacitors disconnected or improperly wired Solution Verify the proper connection of the capacitors Poss...

Reviews: