35
Entering System Parameters
GB
SUPREMATouch
Relay Output Assignment Window
This is not a subwindow of the Measuring Point menu, but an independent window that can only
be reached from the Measuring Point menu. It is used to assign relay outputs to the input selected
in the Measuring Point menu. This window also provides the same function as the
Relay Output
window.
The top three rows of the menu cannot be accessed here and are only shown for information. The
behavior of a relay output depends on its parameter settings and the settings of the appropriate
measuring points.
Fig. 19 Relay output assignment
The functions of the individual window elements are described below:
Field
Field Type
Function
Inhibit
Inputs
Check Box, not
set by default
If enabled, the selected input cannot trigger alarms.
Inhibit
Outputs
Check Box, not
set by default
If enabled, assigned outputs will not be activated in the
event of an alarm or failure of selected measuring points!
During a multiple assignment (Voting), the corresponding
measuring point is ignored when assessing the status. If
enabled for at least one of the measuring points, the inhibit LED
on the MDO as well as the common alarm relay 'Inhibit' starts
flashing with a frequency of 0.5 Hz.
Latch Over-
flow
Check Box, set
by default
If enabled, overflows are latched. This option can not be
disabled for passive sensors.
Zero Band
decimal number,
range is 0..50‰;
20‰ by default
Defines the size of a window around 0 where all measuring
values will be displayed as 0.
All parameter changes using the menu elements described below apply to the relay
output selected in the
Relay
field.
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...