DF-8500 Gas Detector
[M-03] -- Transmitter parameter view
This menu item displays the device information, including gas type, measuring
range, and firmware version.
(1) Press “+” to select the menu item M-03.
(2) Press the “ON” key and the scroll display will s
how “parameter name = parameter
value” which represent the name and content of the parameter displayed. Multiple
parameters can be displayed. Press the “+” or “-” on the submenu to select the
parameter you want to view
(TEST GAS=..., SENSOR USED DAYS=..., GAS=...).
[M-04] -- Calibration parameter setting
This menu item is used to set some parameters that are needed when setting
operation and calibration of the instrument.
(1) Press “+” to select the menu item M-04.
(2) Press “ON” and the screen will display the menu for entering password.
(3) Enter the password (see Section 4.4).
(4) If the password is
correct,
you will enter the next submenu and be able to set
multiple numerous parameters. When you enter the next submenu, the s
croll display
will display "parameter name
= parameter value", which represents
the name and
content of the parameter being set. You will be able to set multiple parameters. The
parameters (TEST GAS
=..., CURRENT OFFSET=...) that need
to change can be
selected by using “+” or “-” in this submenu item.
(5) When the parameters that need to be changed are
addressed, press “ON”
and
then the parameters will flicker to indicate that the device has enter the edit status.
(6) Change the parameters (see Table below).
(7)
After the parameters are changed, you can continue to change other parameters
by pressing “+” or “-
” , or return to the upp
er menu M-04 by pressing “OFF.”
48
Submenu Parameter
Meaning
TEST GAS=
Calibration gas concentration
SENSOR USED DAYS=
Display the time the sensor has been used in days
GAS=
Current gas type configuration
RANGE=
Measuring range
VER=
Firmware version
Z CALI COUNTER=
Number of zero calibration conducted
S CALI COUNTER=
Number of span calibration conducted
Summary of Contents for DF-8500
Page 3: ...DF 8500 1 1 1 DF 8500 SUPREMA Gasgard XL 9010 9020 8020 1 2 4...
Page 4: ...DF 8500 1 3 5...
Page 5: ...DF 8500 1 4 1 2 12 2 2 1 1 DF 8500 6...
Page 7: ...DF 8500 3 3 1 3 1 1 mm 3 DF 8500 8...
Page 21: ...DF 8500 4 2 2 M 01 4 2 2 M 02 OFF 4 4 4 0000 1 2 ON 3 4 5 5 1 M 05 22...
Page 28: ...DF 8500 9 9 1 29 LED 4 20 mA 4mA 4mA E XX 2mA HI 20 5mA BOOT 0mA 0 3 2mA...
Page 33: ...DF 8500 SJ T 11364 GB T 26572 GB T 26572 34 Pb Hg Cd Cr VI PBB PBDE DF 8500...