Automatic battery chargers
CH-105, CH-105-24
25
Malfunction
Possible reasons
To be done
SB is not recharging
The Product’s set charge
voltage is lower than volt-
age level of connected SB
Set relevant charge voltage (see 2.3.5.2)
SB circuit rupture
Switch the Product off. Remove the
rupture. Switch the Product on.
SB malfunction
Replace SB
The Product does not sup-
ply voltage to SB connec-
tion terminals (in case of
not connected SB)
The Product shows zero
voltage without connected
SB
Connect SB to the Product (supply volt-
age to SB connection terminals)
The Product LCD show
zero
SB is not connected to the
product
Connect SB to the Product
Reverse polarity connec-
tion of SB and the Product
Change the polarity
Digital indicators do not
operate
Indication board to central
board flat cable is not con-
nected or disconnected
Connect the tail to the relevant board
connectors
The Product is in energy
saving mode
see 2.3.8
The Product controls do not
work
Buttons board to central
board flat cable is not con-
nected or disconnected
Connect the tail to the relevant board
connectors