5.5
Maintenance Sub-Menu
The maintenance menu enables the operator to view sensor and software versions. MSA Safety technical support has
access to other values as needed. The maintenance menu operation is described in the table below.
Function
Display
Description
Reference
XXXPPM
Default Display
Mode
ALMRSET
Mode Function - Alarm Reset
Mode
CALIB
Mode Function - Calibrate
Mode
SETUP
Mode Function - Set Point Adjustments
Mode
MAINT
Mode Function - Maintenance
Enter
3.XX
Version number of firmware
**
Enter
CCC001
Configuration Version
** Menu Unlock Sequence
Entry into the maintenance menu is protected and requires an unlock sequence to access the next level of menus. The
unlock sequence is executed by pressing the [▲] key 6 times. The firmware revision will be replaced by the first low-level
menu item, “SW Diag”.
Further presses of either the [▲] or [▼] keys will cycle through the “SW Diag”, “HW Diag” or “Version String”.
The software diagnostic options (“SW Diag”) are listed below. Press the [E] key to select any of the sub-menus.
Function
Display
Description
Reference
Unlock
sequence
SW Diag
Software diagnostics sub-menu.
Enter
Panics
Lists number of calls to internal Panic function.
Up
ForceVal
Simulating gas value. Use the [▲] or [▼] keys to select from a series of pre-
defined integer values for simulating a gas concentration. TROUBLE
condition is also available for selection. The same procedure is followed to
CANCEL a simulated gas concentration or TROUBLE condition.
Up
Sen Comm
Displays last PSG command and gas value.
Up
Max Gas
Displays the maximum gas value seen since power-up.
Up
Wait See
5100-99-IT specific. Used to adjust filter on input signal.
Up
Modbus
Display Modbus Register. Use the [▲] or [▼] keys to select from a series of
pre-defined Modbus register ranges, and subsequent individual Modbus
register for display.
30
SMC 5100-XX-IT Toxic Gas Detector Module
5 Operation
US
Summary of Contents for 5100-03-IT
Page 5: ...15 5100 88 IT Dimensions 67 SMC 5100 XX IT Toxic Gas Detector Module 5 US...
Page 20: ...mA Circuit Types 20 SMC 5100 XX IT Toxic Gas Detector Module 4 Installation US...
Page 50: ...12 Modbus Memory Map 50 SMC 5100 XX IT Toxic Gas Detector Module 12 Modbus Memory Map US...
Page 51: ...13 HART SMC 5100 XX IT Toxic Gas Detector Module 51 US 13 HART...
Page 52: ...52 SMC 5100 XX IT Toxic Gas Detector Module 13 HART US...
Page 68: ......