background image

3

mselectronics.co.uk

Positioning

Figure 3 illustrates the typical detection pattern 

of the PIR sensor when the unit is wall-mounted. 

Ensure that the proposed mounting position will 

offer the required area of detection.

High Sensitivity Zone:

 

 

Detects e.g. arm movement.

Low Sensitivity Zone:

 

 

Detects e.g. whole body movement. 

Tips

• 

The sensor is most sensitive to motion across 

its field of view, rather than directly towards or 

away from the sensor.

• 

Avoid mounting the unit close to a light or heat 

source (the one being switched, or otherwise) 

since this may interfere with the detection.

• 

Multiple units may be wired in parallel to 

extend the detection field – see 

Using Multiple 

Detectors

.

Figure 3

 

PIR sensor detection pattern

Electrical Requirements

Before attempting to install the unit, ensure that the intended load and wiring arrangement 

comply with the following requirements. Figure 2 shows a typical wiring example.

• 

3-wire (live/n volt-free switch) connection:

 The unit requires a permanent 

live/neutral connection, and as such is 

not

 suitable for replacing an existing light switch 

with no neutral conductor at the switch location. A volt-free relay output is provided, 

which can be used to switch a load on the same mains supply (by connecting across 

from 

L

 to 

COM

, making 

N/O

 a switched ‘Live Out’), or to provide a contact closure to a 

separate load or control signal. There is no minimum load requirement.

Also available:

 

WMPD2

 / 

WMPAD2

 / 

WMPAD2-L

 (2-wire versions) – Suitable for ‘inline’ 

connection with the load to be switched (no neutral required), such as to replace a 

standard light switch. A minimum load of 

20W (per detector)

 applies; a load capacitor is 

required for smaller loads.

• 

Maximum load:

 The maximum load rating is 

16A (4000W)

, however for high inrush 

loads (such as most types of lighting) a lower limit applies: see 

Technical Specification

.

Summary of Contents for WMPD3

Page 1: ...D3 L today tomorrow and in the future mselectronics co uk Wall Mounted Presence Absence Detectors 3 wire versions WMPD3 Presence Detector WMPAD3 Presence Absence Detector WMPAD3 L with LED indicator e...

Page 2: ...D3 Presence Detector offers fully automatic operation switching on the load upon detection of motion and switching off when the area has been unoccupied for the set period The WMPAD3 Presence Absence...

Page 3: ...iring arrangement comply with the following requirements Figure 2 shows a typical wiring example 3 wire live neutral volt free switch connection The unit requires a permanent live neutral connection a...

Page 4: ...s cable to power the unit If the load is also powered via this wiring ensure the current rating is adequate Otherwise i e if the output is independently powered low current cable may be used Load conn...

Page 5: ...If the unit does not respond to motion during testing remember that the ambient light level must be low enough with respect to the Lux Level setting to permit activation The Lux Level setting only af...

Page 6: ...ighting circuit This method can typically reuse pre existing wiring from a 2 way switching installation where 3 core cable has been used between the switch locations Each unit detects motion independe...

Page 7: ...cted correctly Ensure the load is connected appropriately The relay output is volt free so must be connected suitably to a supply in order to power a load Check that the load works on its own by bypas...

Page 8: ...onics co uk or call 0333 666 1176 Alternatively email techsupport mselectronics co uk Additional copies of this product guide can be downloaded from our website Product Warranty MS Electronics guarant...

Reviews: