Technical Specification
Power supply
220V - 240V AC 50Hz (live/neutral)
Output switch type
Volt-free SPST (normally open) relay
Output switch rating
16A, 250V AC (resistive)
Maximum lighting load
Incandescent: 12A (3000W)
Fluorescent: 10A (2500W)
Compact Fluorescent: 10A (2500W)
Remote input type
Non-isolated, momentary (normally open)
Remote input contact closure timing
Brief (on/reset): 50ms < t < 700ms
Extended (off): t > 1000ms
Time delay selection
3 seconds to 30 minutes or
6 seconds to 60 minutes or
12 seconds to 120 minutes
Mounting hardware
20mm (min.) single-gang UK pattress box
Operating temperature
-10°C to +40°C
Guarantee
5 Years
Weight
87g
Dimensions
86mm x 86mm x 27mm
Fault Finding
Ensure the electrical supply to the unit is isolated before making any adjustments.
!
Load will not switch on
a) Unit is not powered
• Ensure the unit is correctly connected to an active mains supply.
b) Load is not connected correctly
• Ensure the load is connected appropriately. The relay output is volt-free so must be
connected suitably to a supply in order to power a load.
• Check that the load works on its own by bypassing the time delay switch.
c) Remote input is not recognised
• Ensure the input device in use is supported and is correctly connected: see
Remote Input Wiring
.
• Check that the input device (switch or relay output) operates correctly without the
time delay switch connected. For relays, ensure that the contact closure action
conforms to the specified timings (see
Technical Specification
).
Load switches on, but does not switch off (or lighting load flickers)
• Ensure the set period has elapsed since the last remote input contact closure.
•
If attempting to cancel the activation period, ensure that the remote input contact
closure action conforms to the specified timings (see
Technical Specification
).