background image

3

Issue 3.0

Installation

1.  IMPORTANT

: ensure all electrical connections are isolated before commencing any work on the 

unit.

2.  The E925 is designed to be mounted in a 20mm (or deeper) single-gang UK pattress box.

3.  Connect the wiring to the terminal blocks on the humidistat as shown in Figure 1 (or any suitably 

appropriate form). Make sure to choose the correct output terminals that are suitable to your 

application.

4.  Adjust the internal controls to suit the installation operational requirements (see below).

5.  Secure the E925 into the pattress box using the two supplied M3.5 screws.

Operation

1.  IMPORTANT

: ensure all electrical connections are isolated before commencing any work on the 

unit.

2.  Adjust the “Setpoint” dial to the relative humidity the room is to be regulated to.

3.  Set the “Differential” to the total relative humidity swing either side of the “Setpoint” that the 

room humidity is required to keep within.

4.  Example of a typical set-up:

 

Setpoint set to 70% RH, Differential set to 4% RH. 

 

    The unit will maintain the relative humidity between 68% RH and 72% RH.

Technical Specification

Power supply:

220V - 240V AC 50Hz (live/neutral)

“/24V” variant: 22V - 26V AC or DC

Output switch rating:

10A, 250V AC 50Hz (resistive)

Output switch type:

Changeover relay (volt-free)

Humidity control:

5% RH to 95% RH

Humidity differential:

1% RH to 10% RH

Sensor accuracy:

+/- 3% RH

Sensor drift:

+/- 1.2% RH over 5 years (no calibration 

required)

Guarantee:

5 Years

Weight:

97g

Dimensions:

86mm x 86mm x 26.9mm

Notes

1. 

Applying power for the first time

:  The output of the humidistat may not switch in response 

to humidity for up to 30 seconds after first powering on.  This is normal behaviour due to a 

necessary initialisation phase - please wait until this is completed before attempting to test the 

humidistat.  Normal operation will resume as soon as the initialisation phase has completed. 

If the unit has already completed initialisation then short interruptions of power of up to 5 

minutes or more will not trigger the initalisation phase and the humidistat will resume normal 

operation immediately within a couple of seconds.  Power interruptions longer than 5 minutes 

may trigger the initialisation phase again.