Product Overview

The E923 humidistat offers a calibration-free, high accuracy and high quality solution to humidity 

control in an electrical accessory plate form factor.

The E923 regulates to a fully adjustable relative humidity setpoint between 5% and 95%, combined 

with an adjustable relative humidity hysteresis (differential) of anything between 1% and 10%.

3 LED indicators on the front of the unit illustrate the currently detected relative humidity level in

relation to the desired setpoint. The green indicator is illuminated when the sensed humidity is

within the selected differential band around the setpoint. The appropriate red indicator illuminates

to indicate that the sensed humidity is detected as above or below the differential band around the

setpoint.

Product Wiring

1. IMPORTANT

: ensure all electrical connections are isolated before commencing any work on the

unit.

2. Power to the humidistat is provided via the Live and Neutral input terminals labelled “L” and “N”

(230V AC, 50Hz).  On the 24 volt product variant (“/24V”) the same terminals are used (24V AC

or DC) and are not polarity sensitive.

3. A voltage-free changeover relay output capable of switching loads of up to 10A, 250V AC

(resistive) is provided by the humidistat.  Connect to your application in an appropriate manner

given the following:

• The Common “COM” terminal is connected to the Normally Open “NO” terminal when

the relative humidity is sensed to be above the “Setpoint” humidity (use to control

dehumidifiers).

• Conversely, the “COM” terminal is connected to the Normally Closed “NC” terminal

when the relative humidity is sensed to be below the “Setpoint” humidity (use to control

humidifiers).

Figure 1

 

Typical wiring example