MrPEX Systems 5110519 Installation & Operation Manual Download Page 3

©2017 MrPEX® Systems  519_D - 04/17

3 of 16

1-800-716-3406

Choose the placement of the thermostats early in the construction process to 

enable proper wiring during rough-in.
Consider the following:

•  Interior Wall.
•  Keep dry. Avoid potential leakage onto the control.
•  Relative Humidity less than 90%. Non-condensing environment.
•  No exposure to extreme temperatures beyond 32-122°F (0-50°C).
•  No draft, direct sun, or other cause for inaccurate temperature readings.
•  Away from equipment, appliances, or other sources of electrical interference.
•  Easy access for wiring, viewing, and adjusting the display screen.
•  Approximately 5 feet (1.5 m) off the finished floor.
•  The maximum length of wire is 500 feet (150 m).
•  Strip wire to 3/8” (10 mm) for all terminal connections.
•  Use standard 4 conductor, 18 AWG wire.

Installation Location

 ------------------------------------------------------------------------

Materials Required

 ---------------------------------------------------------------------------

•  18 AWG LVT Solid Wire  

(Low Voltage Connections)

Removing The Thermostat Base

To remove the thermostat base:

•  Locate the tab on the bottom of the 

thermostat.

•  Push the tab with either your thumb or 

with a screwdriver.

•  Lift the thermostat front away from the 

thermostat’s base.

Summary of Contents for 5110519

Page 1: ...a display with large type make this thermostat easy to read and use A Slab Sensor 5110079 is included to measure floor temperature to protect the floor from overheating and enhance comfort This easy t...

Page 2: ...ing the Thermostat Wiring 10 User Interface 11 Home Screen 11 Symbols Description 11 Sequence of Operation 12 Heating Operation 12 Programmable Settings 13 Troubleshooting 14 Error Messages 14 Frequen...

Page 3: ...dings Away from equipment appliances or other sources of electrical interference Easy access for wiring viewing and adjusting the display screen Approximately 5 feet 1 5 m off the finished floor The m...

Page 4: ...wall anchors Terminate wiring to the wiring strip Push the thermostat front onto the thermostat base 3 1 4 83 mm Stud Gang Box Thermostat Front Thermostat Base Adapter Plate 5110012 If a single gang b...

Page 5: ...f sufficient depth the 5110079 slab sensor can be placed directly into either the thin set material or the thin pour material and covered over Ensure that the sensor is located in such a position that...

Page 6: ...tion into a 6 150 mm by 6 150 mm square A groove 3 16 5 mm wide by 3 16 5 mm deep by 1 3 4 45 mm long should be cut into the insulation to accommodate the sensor Place the sensor in the groove and san...

Page 7: ...lose If the test meter reads a very high resistance there may be a broken wire a poor wiring connection or a defective sensor If the resistance is very low the wiring may be shorted there may be moist...

Page 8: ...105 41 5 210 110 43 4 665 115 46 4 184 120 49 3 760 125 52 3 383 130 54 3 050 135 57 2 754 140 60 2 490 145 63 2 255 150 66 2 045 155 68 1 857 160 71 1 689 Temperature Resistance F C 165 74 1 538 170...

Page 9: ...No Power C 519 R Rh W1 S1 Com No Power Zone Valve 24 V ac Transformer L N R C Slab Sensor 5110079 N Relay C 518 R Rh W1 S1 Com No Power R C 2 1 8 7 3 4 5 6 C 519 R Rh W1 S1 Com No Power LG 115 V ac S...

Page 10: ...ostat display intially powers on but later shuts off intermittantly there may be a short circuit from the W wire to ground or the power supply is too small to power the load Testing the Heat Zone Outp...

Page 11: ...n Heat is turned on MODE OFF The heating system is off Warning Symbol Indicates an error is present MIN The floor is at or below the floor minimum temperature Max The floor has reached the floor maxim...

Page 12: ...or is turned on and a floor sensor is connected the thermostat will maintain the desired air temperature as well as a minimum floor temperature This operation is recommended for areas with large windo...

Page 13: ...umber Hold the button to view the software version ESCAPE Release the and buttons to return to the home screen Installer settings Press the and buttons together for 5 more seconds auxiliary sensor Sel...

Page 14: ...perature sensor has a short circuit fault Do not confuse this error with the auxiliary room sensor short circuit error This error cannot be field repaired Contact your wholesaler or MrPEX Systems sale...

Page 15: ...Relay 30V ac dc 2 A Class 2 circuits Sensor NTC thermistor 10 k 77 F 25 C 0 2 C 3892 Included Slab Sensor 5110079 Optional tekmar type 070 072 073 076 077 079 084 Frequently Asked Questions Symptom L...

Page 16: ...tation or labor charges unless such charges are authorized in writing in advance by MrPEX Systems Any repairs without the express written consent of MrPEX Systems shall render this Limited Warranty in...