MrHeater MHVFDF20BFT Operating Instructions And Owner'S Manual Download Page 5

5

Installation Instructions and Owner’s Manual

Universal Unvented Room Heater

Note:

 the space includes the room in which you 

install heater plus any adjoining rooms with doorless 
passageways or ventilation grills between the rooms.

1.  Find the volume of the space by multiplying room length 

x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.  
 

(height) = 2592

If additional ventilation to adjoining room is supplied with 
grills or openings, add the volume of these rooms to the 
total volume of the space.

2.  Divide the space volume by 50 cubic feet to determine the 

maximum Btu/hr the space can support.

Example:   2592 cu.ft. (volume of space) / 50 cu.ft. =  
 

51.8 or 51,800 (maximum Btu/hr the space  

 

can support)

 WARNING:

 This heater shall not be installed in a 

room or space unless the required volume of indoor 
combustion air is provided by the method described 

in the National Fuel Gas Code, ANSI Z223.1/NFPA 

54, the International Fuel Gas Code, or applicable 
local codes

3.  Add the Btu/hr of all the fuel-burning appliances in the 

space such as, Vent–free heater, Gas water heater, Gas 

furnace, Vented gas heater, Gas fireplace logs, and Other 
gas appliances*

*Do not include direct-vent gas appliances. Direct-vent 

draws combustion air from the outdoors and vents to 
the outdoors.
Example:

Gas water heater 

40,000 Btu/hr

Vent Free   20,000 Btu/hr
Total 

 

=60,000 Btu/hr

4.  Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the    

 

space can support)

 

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confined space 

because the actual Btu/hr used is more than the 
maximum Btu/hr the space can support.

You must provide additional fresh air. Your options are 
as follows:

A. Rework worksheet, and the space of an adjoining room. 

If the extra space provides an unconfined space, remove 
door to adjoining room or add ventilation grills between 

the rooms. See Ventilation From Inside Building (Fig. 2)

B.  Vent room directly to the outdoors. See Ventilation From 

Outdoors (Fig. 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size makes 

room unconfined. 

If actual Btu/hr used is less than the maximum Btu/

hr the space can support, the space is an unconfined 
space. You will need no additional fresh air ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 
space. When ventilation to an adjoining unconfined space, 

you must provide two permanent openings: one within 12” 
of the ceiling and one within 12” of the floor on the wall 
connecting the two spaces (see options 1 & 2 of figure 2). 

You can also remove door into adjoining room (see option3, 

fig 2). Follow the National Fuel Gas Code NFPA 54/ ANSI 
Z223.1, Section 5.3, Air for Combustion and Ventilation for 

required size of ventilation grills or ducts.

WARNING:

 Rework worksheet, adding the space of 

the adjoining unconfined space. The combined space 
must have enough fresh air to supply all appliance in 
both spaces. 

Ventilation from Outdoors

If necessary provide extra fresh air by using ventilation grills 
or ducts. Connect these items directly to the outdoors or 
spaces open to the outdoors. These include attics* and 
crawl spaces. Follow the National Fuel Gas Code NFPA 

54/ ANSI Z223.1, Section 5.3, Air for Combustion and 

Ventilation for required size of ventilation grills or ducts.

Ventilation 
Gills into 
Adjoining 
Room - 
Option 1

Ventilation Gills into Ad-
joining Room - Option 2

12”

12”

Or remove 
door into 
Adjoining 
Room - 
Option 3

Figure 2

INLET 
AIR

OUTLET 
AIR

VENTILATION CRAWL SPACE

TO CRAWL 
SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 
ATTIC

OUTLET AIR

Figure 3.

*IMPORTANT:

 Do not provide openings for inlet or 

outlet into attic. If attic has a thermostat-controlled power 

vent, heated air entering the attic will activate the power 
vent.

Summary of Contents for MHVFDF20BFT

Page 1: ...our gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier This is an unvented gas fired heater It uses air oxygen...

Page 2: ...including benzene which is known to the state of California to cause cancer and cause birth defects or other reproductive harm for more information go to www P65Warnings ca gov Due to high temperature...

Page 3: ...ilation page 4 3 Keep all air openings in heater clear free of debris or any blockage This will ensure that enough air for proper combustion enters the heater 4 If heater shuts off do not relight unti...

Page 4: ...1 000 Btu per hour 4 8 m3 per kW of the aggregate input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed through openi...

Page 5: ...g room If the extra space provides an unconfined space remove door to adjoining room or add ventilation grills between the rooms See Ventilation From Inside Building Fig 2 B Vent room directly to the...

Page 6: ...l by using the floor mounting stands included with the heater If installed on combustible flooring such as carpeting tile or other combustible material other than wood flooring the heater must be plac...

Page 7: ...s at marked locations using 9 64 drill bit 2 Place mounting bracket onto wall Line up holes on each end of bracket with hole drilled in wall 3 Insert mounting screws through bracket and into wall stud...

Page 8: ...line Gas line pressure must be no greater than 10 5 inches of water If gas line pressure is higher heater regulator damage could occur PROPANE LP CAUTION Never connect heater directly to the Propane s...

Page 9: ...equal to or less than psi 3 5 kPa 2 Cap off open end of gas pipe where equipment shutoff valve was connected 3 Pressurize supply piping system by either using compressed air or opening main gas valve...

Page 10: ...seconds Note The first time that the heater is operated after connecting the gas supply the control knob should be depressed for about 30 seconds This will allow air to bleed from the gas system 6 Wi...

Page 11: ...ease follow the directions on the can If you don t follow directions on the can you could damage the burner or pilot assembly In addition the directions below should also be followed 1 Shut off the un...

Page 12: ...allows thermocouple to cool causing pilot flame to go out This problem could be caused by one or both of the following a Low gas Pressure b Dirty or Partially clogged ODS pilot a Contact local gas co...

Page 13: ...or replace burner orifice White powder residue forming within burner box or on adjacent walls or furniture When heated vapors from furniture polish wax carpet cleaners etc turn into white powder resid...

Page 14: ...ssories may be purchased at any Mr Heater Products local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 866 447 2194 WWW HEATSTARBYENERCO COM Our office hour...

Reviews: