MrHeater MHVFDF10BF Operating Instructions And Owner'S Manual Download Page 9

9

Installation Instructions and Owner’s Manual

Universal Unvented Room Heater

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for 

leaks after installing or servicing. Correct all leaks at 
once. 

WARNING: Never use an open flame to check for a gas 

leak. Apply a mixture of liquid soap and water to all 
joints. Bubbles forming show a leak. Correct all leaks 
at once. 

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
High Pressure 

Test pressure in Excess of ½ psig (3.5kPa)

1. The appliance and its appliance main gas valve must be 

disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures 
in excess of 

½ 

 psi (3.5 kPa). The appliance must be 

isolated from the gas supply piping system by closing its 
equipment shutoff valve during any pressure testing of 
the gas supply piping system at test pressures equal to 
or less than 

½

 psi (3.5 kPa).

2. Cap off open end of gas pipe where equipment shutoff 

valve was connected.

3. Pressurize supply piping system by either using 

compressed air or opening main gas valve on or near 
gas meter.

4. Check all connections and joints in gas supply piping 

system. Apply mixture of liquid soap and water to gas 
joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Depressurize and relieve pressure in supply piping 

system.

7. Reconnect heater and equipment shutoff valve to gas 

supply. 

8. Reconnected fittings must be checked for leaks in next 

section. 

Low Pressure

Test Pressure Equal To or Less Than ½ psig (3.5 kPa)

1. Close equipment shutoff valve (see figure 13).

2. Pressurize supply piping system by either using 

compressed air or opening propane/LP supply valve.

3. Check all joints from the propane/LP supply valve to 

equipment shutoff valve (see figure 14). Apply mixture 
of liquid soap and water to gas joints. Bubbles forming 
show a leak.

4. Correct all leaks at once.
5. Depressurize and relieve pressure from supply piping 

system.

Pressure Testing Heater Gas Connections:

1. Make sure that the heater supply piping system is 

connected and has been leak tested as described above.

2. Make sure control knob of heater is in OFF position.

3. Open equipment shutoff valve (see figure 13). 
4. Open propane/LP supply valve.

5. Check all joints from equipment shutoff valve to control 

valve (see figure 14). Apply mixture of liquid soap and 
water to gas joints. Bubbles forming show a leak.

6. Correct all leaks at once.

7. Light heater (see Operating Your Heater, page page 

10.)

8. Turn off heater (see To Turn OFF Gas to Appliance, 

page 10.)

9. Replace lower front panel. 

OPERATING YOUR HEATER

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: If you do not follow these instructions 

exactly, a fire or explosion may result causing property 
damage, personal injury or loss of life. 

A. This appliance has a pilot that must be lighted by hand. 

When lighting the pilot, follow these instructions 
exactly.

B.  BEFORE LIGHTING smell all around the appliance area 

for gas. Be sure to smell next to the floor because some 
gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

• 

Shut off gas supply.

• 

Do not try to light any appliance.

• 

Do not touch any electrical switch; do not use any 

phone in your building.

•  Immediately call you gas supplier from a neighbor’s 

phone. Follow the gas supplier’s instructions.

• 

If you can not reach your gas supplier, call the fire 
department.

Equipment 
Shutoff Valve

Open

Closed

Figure 13

Control Valve

Equipment 
Shutoff Valve

To regulated propane source

Figure 14

Summary of Contents for MHVFDF10BF

Page 1: ...the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier T...

Page 2: ...including benzene which is known to the state of California to cause cancer and cause birth defects or other reproductive harm for more information go to www P65Warnings ca gov Due to high temperature...

Page 3: ...servicing Only a qualified service person should service and repair heater 6 Do not run heater Where flammable liquids or vapors are used or stored During dusty conditions 7 Before using furniture po...

Page 4: ...s Code or applicable local codes 3 Add the Btu hr of all the fuel burning appliances in the space such as Vent free heater Gas water heater Gas furnace Vented gas heater Gas fireplace logs and Other g...

Page 5: ...ion and Ventilation for required size of ventilation grills or ducts WARNING Rework worksheet adding the space of the adjoining unconfined space The combined space must have enough fresh air to supply...

Page 6: ...floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next to vinyl or cloth...

Page 7: ...using 5 16 drill bit For solid walls concrete or masonry drill at least 1 deep 2 Fold wall anchor as shown in figure 8 below 3 Insert wall anchor wings first into hole Tap anchor flush to wall 4 For t...

Page 8: ...ust connect heater to gas supply Follow all local codes WARNING This appliance requires a 3 8 NPT National Pipe Thread inlet connection to the pressure regulator Use of floor mounting feet will requir...

Page 9: ...opane LP supply valve 3 Check all joints from the propane LP supply valve to equipment shutoff valve see figure 14 Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 4 Co...

Page 10: ...supplier for repairs Until repairs are made light pilot with match 7 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If pilot does not stay lit r...

Page 11: ...he can you could damage the burner or pilot assembly In addition the directions below should also be followed 1 Shut off the unit including the pilot Allow the unit to cool for at least thirty minutes...

Page 12: ...ose at control valve Hand tighten thermocouple nut until snug and then tighten 1 4 turn more Pilot flame not touching thermocouple which allows thermocouple to cool causing pilot flame to go out This...

Page 13: ...clearances see Figure 4 page 6 Dirty or partially clogged burner orifice Clean burner orifice see Cleaning and Maintenance on page 1 1 or replace burner orifice White powder residue forming within bu...

Page 14: ...e purchased at any Mr Heater Products local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 866 447 2194 WWW HEATSTARBYENERCO COM Our office hours are 8 00 AM...

Reviews: