Fig. 2
High limit value : 100
Low limit value : 20
Hysteresis value : 5
* The control relay will On when measuring
value up to 100. The control relay will Off
again when measuring value down to 95.
* The control relay will On when measuring
value down to 20. The control relay will
Off when measuring value up to 25.
Offset value setting
1)After finish the Hysteresis setting, press the
" Set Button " ( 3-4, Fig. 1 ) twice, the " Display "
will show " oFSt ", now the meter is ready for the
the offset value setting.
2)Use the " Button " ( 3-5, Fig. 1 ) and the "
▼
▲
Button " ( 3-6, Fig. 1 ) to adjust the desiring
offset value.
* When adjust the Offset value, the " SV indicator "
( 3-3, Fig. 1 ) will light.
10