7 Fault elimination
Maschinenfabrik Reinhausen GmbH 2020
129
4983703/01 EN
VACUTAP
®
VV-Ex
7.1.2 Flap valve in OFF position
If the flap valve is in the OFF position, proceed as follows:
1. Ensure that the transformer is not started up under any circumstances.
2. Contact and inform Maschinenfabrik Reinhausen of the following:
ð
Serial number of protective relay and on-load tap-changer
ð
What was the load of the transformer at the instant of tripping?
ð
Was the on-load tap-changer moved immediately before or during trip-
ping?
ð
Did any other protective devices of the transformer respond at the in-
stant of tripping?
ð
Were switching operations in the network being carried out at the in-
stant of tripping?
ð
Were overvoltages registered at the instant of tripping?
3. Take further action in agreement with Maschinenfabrik Reinhausen.
7.1.3 Re-commissioning the transformer
Once the reason for the protective relay tripping has been established and
remedied, you can re-commission the transformer:
1. Check the protective relay.
2. Commission the transformer.