5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
41
7545652/00 EN
VACUTAP
®
VR-Ex
2. Fit stud bolts on mounting flange.
Figure 16: Tracing template, stud bolts
5.3 Installing the on-load tap-changer in the transformer
(standard version)
5.3.1 Fastening on-load tap-changer to transformer cover
5.3.1.1 Fastening oil compartment to transformer cover – standard on-load
tap-changer head version
You can lower the oil compartment of on-load tap-changers with U
m
<
362 kV through the opening in the mounting flange without separating the
top part of the on-load tap-changer head from the bottom part.
1.
CAUTION!
An unstably positioned oil compartment may tip over, re-
sulting in injuries or property damage. Place the oil compartment on a
level surface and secure it against tipping.
2. Remove red-colored packaging material and transport material from the
oil compartment.