7 Functions and settings
Maschinenfabrik Reinhausen 2014
134
222/08 EN
TAPCON® 240
Setting number of attempts to transmit unsolicited messages
This parameter is used to set the maximum number of attempts to transmit
unsolicited messages.
If the device receives no release for data transmission through the Master
(for example, in case of transmission errors), then the data transmission is
repeated in accordance with the set maximum number of send attempts.
This display is only provided for the following interface protocol:
▪
DNP3
The voltage regulator must be restarted after changing this setting.
To set the maximum number of attempts to transmit unsolicited messages,
proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Comm. interface 1 > Press
until the desired parameter is displayed.
ð
Repeat unsolicited messages CIC1.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The maximum number of attempts to transmit unsolicited messages is
set.
Timeout for application confirm responses
You can use this parameter to define the permissible time which the device
waits for the following feedback from the master device:
▪
Application confirmation response
▪
Confirmation of unsolicited message
If the permissible time is exceeded, another transmission request is sent to
the master device. The number of requests sent is dependent on the set
number of attempts to transmit unsolicited messages [
This display is only provided for the following interface protocol:
▪
DNP3
To set the timeout for application confirm responses, proceed as follows:
7.14.10
7.14.11