5 Installation and commissioning
35
BA5831400-00 EN
5.3.2 Securing the capillary line
When securing the capillary line, note the following information:
NOTICE
Damage to the device!
A capillary line bending radius that is too narrow can lead to a loss of de-
vice function!
► Ensure compliance with the minimum bending radius of 50 mm (1.97").
▪ Attach the capillary line to the transformer so that it cannot be damaged
during transport or operation, due to factors such as impact, scuffing,
pressure, vibrations or crushing.
Proceed as follows:
1. Route the capillary line to the transformer and secure it with cable ties.
2. Wind up any excess capillary line with a minimum winding diameter of
80 mm (3.15").
5.3.3 Inserting the temperature sensor
1. Fill 2/3 of the thermometer pocket of the transformer with oil or heat-con-
ducting paste.
Figure 15: Filling the thermometer pocket
Summary of Contents for MESSKO MT-ST Compact
Page 25: ...3 Product description 25 BA5831400 00 EN 3 6 Nameplate Figure 9 Nameplate ...
Page 78: ...8 Disposal 78 BA5831400 00 EN Observe the national disposal regulations in the country of use ...
Page 90: ...10 Appendix 90 BA5831400 00 EN NPT adapters optional Figure 73 NPT adapters 1 2 NPT 3 4 NPT ...
Page 91: ......