11 Technical data
49
BA5789879-01 EN
Operating conditions
MESSKO® MPREC®
Site of operation
Indoors and outdoors, tropicalized
Operating temperature
Ambient tem-
perature:
-50°C...+80°C (mechanical version
only)
-40°C...+80°C (version with micro-
switches)
Oil tempera-
ture:
-30°C...+120°C
Storage temperature
-50°C...+80°C
Degree of protection
(terminal box, cable
screw connections, mi-
cro-switches)
IP65 in accordance with IEC 60529
IP66 in accordance with IEC 60529 available as an op-
tion for:
▪ Standard protective cover with cable screw connec-
tion
▪ OD protective cover with cable screw connection
▪ OD protective cover with terminal box
Contamination level
3
Overvoltage category
III; external protection: miniature circuit breaker maxi-
mum 16 A, C characteristic
Materials
MESSKO® MPREC®
All parts
Weather resistant and transformer-oil resistant; all exter-
nal parts UV resistant
Offshore version: all external parts also seawater resis-
tant
Device flange
Seawater-proof aluminum casting
Standard protective cover Seawater-proof aluminum with powder coating
RAL 7033 or RAL 7038