5 Mounting
35
BA5789879-01 EN
Establishing operational readiness
1. Screw the signal pin cap onto the signal pin using 2 open-ended
wrenches, wrench size 12 and 32, with max. torque = 8 Nm.
Figure 13: Mounting signal pin
2. Push the signal pin into the device as far as it will go.
3. If the device is equipped with a semaphore, fold this down so that its lower
edge is perpendicular to the signal pin. Otherwise the pressure relief de-
vice is visually and electrically in the tripped position.
ð
This ensures that the pressure relief device is visibly in the operating posi-
tion.
5.3 Electrically connecting the pressure relief device
WARNING
Danger of death or severe injury!
Danger of death or severe injury due to improper electrical
connection of the pressure relief device.
► When the pressure relief device trips, the transformer must be immedi-
ately de-energized by the circuit breaker.
► Ensure that the pressure relief device's signaling contact is correctly
looped into the tripping circuit of the transformer circuit breaker.