Once the switch-on delay has elapsed, the cooling stages are activated. To
limit the inrush current of the cooling stages, they are activated one after an-
other with a delay time of 60 seconds.
Settings
Parameters
Cooling ...rol
Name
Value
Operating mode
Manual
Load-dep. mode
Off
Load-dep. mode: Switching point
100.0 %
Load-dep. mode: Switch-on delay
2.0 min
Load-dep. mode: Overrun time
30.0 min
Activate period. mode
Off
Period. mode: Interval
24 h
Period. mode: Switch-on duration
30 min
Period. mode: Switch-on delay
120 min
Activate altern. mode
Off
Altern. mode: Change interval
24 h
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 10:14
Figure 87: Cooling system control
To use this function, you need to activate the corresponding cooling stage
[
1. Go to
Settings > Parameters > Cooling system > Cooling system con-
trol
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Activate load-dependent mode
You can use this parameter to activate the load-dependent mode of the cool-
ing system control.
Load-dependent mode: Switching point
You can use this parameter to set the switching threshold as a percentage in
relation to the nominal current of the transformer. All cooling stages are acti-
vated if the load current of the transformer is greater than the set switching
point.
Load-dependent mode: Switch-on delay
You can use this parameter to set the delay time for switching on the first
cooling stage.