9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
119
4453918/14 EN
ETOS
®
TD
If you enter event number 500, the link is disabled.
9.10 Cooling system control (optional)
You can use the cooling system control function package to control and/or
monitor up to 6 cooling stages depending on device configuration.
9.10.1 Configuring cooling stages
To control the cooling system, you have to set the following parameters for
each cooling group:
Settings
Parameters
Control, c...p 1
Name
Value
Activate
On
Switch-on input variable
Hot-spot temperature
Switch-off input variable
Top-oil temperature
Switching point
60°C
Hysteresis
5 K
Switch-on delay
2 min
Activate altern. mode
On
Activate period. mode
On
Active if error
On
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
23.09.2020 09:23
Figure 86: Cooling stage
1. Go to
Settings > Parameters > Cooling system > Cooling group X
control
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Activate
You can use this parameter to activate or deactivate the cooling stage.
▪ On: The cooling stage is used for cooling system control.
▪ Off: The cooling stage is not used for cooling system control.
Activate cooling stage X
In the "Manual" operating mode [
Section 9.10.2, Page 121], you can use
this parameter to start and stop the cooling stage.