background image

7

Enerco Group, Inc. | Kerosene Forced Air Heater

Operating Instructions and Owner’s Manual

DIAGNOSTIC SAFETY SHUTDOWN AND TROUBLE SHOOTING:

These instructions are applicable for TS75KT, TS125KT, TS175KT, TS210KT.
This heater is equipped with a diagnostic control board and flashing LED error indicator. This flashing LED signals when there is a
malfunction of a monitored component. See the following diagnostic Guide for error messages and a brief description of the error.
Follow the step-by-step trouble shooting guide to correct the cause of the error message.

LED

CAUSE

TROUBLE SHOOTING

E1

No Flame

1)

Check wiring to Cad Cell (per wiring schematic in manual).
Test heater.

2)

Clean Cad Cell photo cell.
a) Slide Cad Cell out of Cad Cell holder.
b) Push the photo cell out of the white rubber Cad Cell housing by
    pushing on the blue and white wires.
c) Clean the photo cell with a soft cloth and rubbing alcohol.
d) Pull the photo cell back into the Cad Cell housing and reinstall into

holder.

e) Test heater.

3)

If the heater still does not operate, replace Cad Cell.
Test heater.

4)

Replace oil flame control assembly.
Test heater.

E2

Room Thermometer Failure

1)

Digital Thermometer Failure - Replace Thermometer

E3

Thermostat Up Key Failure

1)

Thermostat setting will not increase - check thermostat.

2)

Disconnect and reconnect the pick-up connector on control board
(small white plug connector).

3)

Still not functioning, replace thermostat.

E4

Thermostat Down Key Failure

1)

Thermostat setting will not decrease - check thermostat.

2)

Disconnect and reconnect the pick-up connector on control board
(small white plug connector).

3)

Still not functioning, replace thermostat.

E5

Over-heat

1)

High Limit Switch activation

2)

Allow heater to cool off.

3)

Restart heater.

E6

Reset button Error

1)

Check wiring to reset button.

2)

Replace reset button.

3)

Replace oil flame control assembly.

Summary of Contents for TS125KT

Page 1: ...sion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Service must b...

Page 2: ...70277 Rev C 04 07...

Page 3: ...FOR HOME OR RECREATIONAL VEHICLE USE WARNING YOUR SAFETY IS IMPORTANT TO YOU AND TO OTHERS SO PLEASE READ THESE INSTRUCTIONS BEFORE YOU OPERATE THIS HEATER The State of California requires the followi...

Page 4: ...people the user is responsible for properly acquainting those present with the safety precautions and instructions and of the hazards involved SAFETY PRECAUTIONS 1 Check the heater thoroughly for dama...

Page 5: ...an with a long fill spout IMPORTANT Before filling fuel tank the first time or after extended storage periods drain the fuel tank of any moisture or condensation 4 Locate heater at a safe distance fro...

Page 6: ...ould not be used to clean this filter Reinstall cleaned filter in filter body in the same position as it was when removed If the filter appears extremely dirty replace it with a new filter of the same...

Page 7: ...ue and white wires c Clean the photo cell with a soft cloth and rubbing alcohol d Pull the photo cell back into the Cad Cell housing and reinstall into holder e Test heater 3 If the heater still does...

Page 8: ...70277 Rev C 04 07 8 Enerco Group Inc Kerosene Forced Air Heater Operating Instructions and Owner s Manual...

Page 9: ...9 Enerco Group Inc Kerosene Forced Air Heater Operating Instructions and Owner s Manual...

Page 10: ...ties express or implied Specifically there is no warranty of fitness for a particular purpose and there is no warranty of merchantability In no event shall the Company be liable for delay caused by im...

Reviews: