background image

The TE8001 is an electronic non-programmable thermostat. It is designed to work with most
standard single stage heating and/or single stage cooling systems. These include single or dual
transformer 24 VAC gas, oil or electric heating, and 24 VAC cooling systems. This thermostat
is also compatible with single stage heat pumps.
The TE8001 is designed to operate entirely on two AAA alkaline batteries, or 24 volts from the

heating/cooling system’s transformer, using the batteries only for memory back up.

FORM: 8063
       Rev: -

Installation:

 Important: Read the entire instructions before beginning installation. Failure to follow these
instructions could result in personal injury and/or property damage.

Location:

The thermostat should be mounted 4 to 5 feet above the floor in a location where it will be
exposed to average room temperature. The thermostat must not be mounted where it will be
effected by a source of heat such as lamps, sunlight, fireplaces, pipes, registers, etc..., or
sources of cold such as windows, doors, drafts, etc... The thermostat must not be mounted on
an exterior wall, behind a door, or in an alcove. Such locations will inhibit the thermostat’s

ability to accurately control room temperature

Removing existing thermostat:
Caution:

Power must be disconnected before removing existing wiring connections from thermostat to
prevent possible electrical shock and/or equipment damage. All wiring must conform to local
and national electrical codes and regulations.
1: Remove existing wiring by writing down each of the wire’s colors and the designation of the
terminals that they are connected to. If more than one wire has the same color, tag the wire
with some form of identification.
2: Remove wires from thermostat.

Mounting:

This thermostat may be mounted directly to the wall, by using the mounting screws supplied.
Remove base from front section, by opening battery door, remove batteries. Pull case apart.
To mount directly to a wall use holes located in top and bottom of case.
Pull wires through hole in center of case.

Do not depend upon the thermostat as the sole means

of disconnecting power when installing or servicing the product it is
controlling. Always disconnect power at the main circuit breaker as
described above. Failure to do so may result in fatal electric shock.

1

4

TE8001 Installation & Operation Manual

TPI Corporation, Johnson City, TN 37602

Tel: 423-477-4131, Fax:423-477-0545

Diagram 3:  Single Stage Heat Pump

1: Connect the transformer hot wire to the RC terminal.
2: Connect jumper between RC and RH terminals
3: Connect compressor to the Y terminal.
4: Connect jumper wire between the Y and W terminals.
5: Connect Fan to G terminal
6: Connect reversing valve to O terminals if reversing valve is activated in the
cool mode (most common), or to the B terminal if reversing valve is to be acti-
vated in the heating model.
7: Connect transformer common wire to C terminal (optional) if you wish thermo-
stat to be powered from the transformer. Without this connection, thermostat will
be powered from AAA batteries.

G

Y RC RH W C

B

O

WIRING DIAGRAM 3.

Installing Thermostat onto base:

Once the wires have been connected to the base, and the options selected, it is
time to install thermostat onto the base.  Close the battery compartment door. Do
not install batteries yet. Align the thermostat with base, and push together. Open

battery door and install batteries.

Operation:

1: Select Heat or Cool with Heat/Off/Cool Switch:
2: The display will indicate current room temperature, and display a flame if the
heat mode has been selected or a snow flake if the cool mode has been selected.
3: Press up or down arrow to set desired temperature. “SET TEMP” will appear in
the display to indicate you are setting the temperature.
4: Whenever the thermostat is activating the heating or cooling system, the word
“ON” will appear in the display.
5: Whenever you change modes (from heat  to cool or cool to heat), the
thermostat will remember the last  temperature set in that mode. The heat setting
and cooling setting do not have to be the same.

Summary of Contents for TE8001

Page 1: ...ount directly to a wall use holes located in top and bottom of case Pull wires through hole in center of case Do not depend upon the thermostat as the sole means of disconnecting power when installing...

Page 2: ...the middle and lower two pins TH This activates the fan whenever the thermostat turns the cooling on For an electric heat system place the jumper on the middle and upper pins H C which will allow the...

Page 3: ...ator appears 5 LCD Pattern Description a 2 Large digits for room temperature readout b 4 small bars for 0 2 0 4 0 6 0 8 degree indication c SET TEMP indicator for control temperature setting indicatio...

Page 4: ...limitations on how long an implied warranty lasts The above exclusions or limitations may not apply to you During the warranty period TPI Corporation will at its sole option repair or replace any def...

Page 5: ......

Page 6: ...nstalled in the horizontal position the adjustment lever must extend out the right side of the thermostat If installed in the vertical position the lever must extend out the bottom of the thermsotat 3...

Page 7: ...of the thermostat 6o to 8o F above the room temperature The A C system should turn off The fan may have a delay before it turns off Heating Cooling Model UT8001 1 Turn on power to the heating cooling...

Page 8: ...ing air conditioning and heating ducts Do not install where anything can obstruct free air flow such as drapes or doors 2 Disconnect the power supply to the air conditioning and heating system 3 Gentl...

Page 9: ...ntaining air conditioning and heating ducts Do not install where anything can obstruct free air flow such as drapes or doors 2 Disconnect the power supply to the air conditioning and heating system 3...

Page 10: ...eating ducts Do not install where anything can obstruct free air flow such as drapes or doors 2 Disconnect the power supply to the air conditioning and heating system 3 Gently remove the cover of the...

Page 11: ...y or field installed locking kits for top and for bottom setting and 6 wire leads W W W W WARNING ARNING ARNING ARNING ARNING IF THIS PRODUCT IS USED TO REPLACE A DE VICE CONTAINING MERCURY THE PUR CH...

Page 12: ...t sense the average temperature of the area to be controled Do not mount the thermostat adjacent to water pipes in drafty areas or other locations that would adversely affect the operation of the ther...

Page 13: ...C COOL NC NO C L1 L2 HEAT NC NO C L1 L2 COOL L1 L2 NC NO C L1 NC NO C HEAT L2 COOL CHANGE OVER SWITCH L1 NC NO C HEAT COOL L2 CHANGE OVER SWITCH DIAGRAMS FIG 1 FIG 2 TYPICAL WIRING DIAGRAMS TO BE PRO...

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ...ontrolled space Do not mount near windows doors or direct sunlight 2 Remove the thermostat cover Position the box with the wiring hole oriented as desired Fasten the box to the wall with 2 3 screws th...

Reviews: