background image

5

Installation Instructions and Owner’s Manual

Unvented Natural Gas Vent Free Room Heaters

*Adjoining rooms are communication only if there 

are doorless passageways or ventilation grills be-

tween them.

DETERMINING THE TYPE OF HEATER 

LOCATION SPACE:

Use this method to determine if you have a confined or 

unconfined space.

Note:

 the space includes the room in which you 

install heater plus any adjoining rooms with doorless 

passageways or ventilation grills between the rooms.

1. Find the volume of the space by multiplying room 

length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.  

 

(height) = 2592

If additional ventilation to adjoining room is supplied 

with grills or openings, add the volume of these rooms 

to the total volume of the space.
2. Divide the space volume by 50 cubic feet to deter-

mine the maximum Btu/hr the space can support.

Example: 2592 cu.ft. (volume of space) / 50 cu.ft. =  

 

51.8 or 51,800 (maximum Btu/hr the space  

 

can support)

WARNING:

 If the area in which the heater may be 

operated is smaller than defined as an unconfined 

space or if the building is of unusually tight con-

struction, provide adequate combustion and ventila-

tion air by the methods described in the 

National 

Fuel Gas Code, NFPA 54/ ANSI Z223.1, 

Section 

5.3 or applicable local codes. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 

heater, Gas furnace, Vented gas heater, Gas fire-

place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and 

vents to the outdoors.
Example:  Gas water heater 

40,000 Btu/hr

 

 

Vent Free  

20,000 Btu/hr

 

 

Total   

 

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.

Example:   51,800 Btu/hr (maximum Btu/hr the  

 

 

space can support)

 

 

60,000 Btu/hr (Actual amount of Btu/hr  

 

 

used)

The space in the above example is a confined 

space because the actual Btu/hr used is more than 

the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 

are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfined 

space, remove door to adjoining room or add venti-

lation grills between the rooms. See Ventilation Air 

From Inside Building (Figure 2).

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Figure 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfined. 

If actual Btu/hr used is less than the maximum Btu/

hr the space can support, the space is an uncon-

fined space. You will need no additional fresh air 

ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 

space. When ventilation to an adjoining unconfined 

space, you must provide two permanent openings: one 

within 12” of the ceiling and one within 12” of the floor 

on the wall connecting the two spaces (see options 1 

& 2 of fig. 2). You can also remove door into adjoin-

ing room (see option3, fig 2). Follow the National Fuel 

Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for 

Combustion and Ventilation for required size of ventila-

tion grills or ducts.

Figure 2.

Figure 3.

Ventilation 

Gills into 

Adjoining 

Room - 

Option 1

Ventilation Gills into 

Adjoining Room - Option 2

12”

12”

Or remove 

door into 

Adjoining 

Room - 

Option 3

INLET 

AIR

OUTLET 

AIR

VENTILATION CRAWL SPACE

TO CRAWL 

SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 

ATTIC

OUTLET AIR

Summary of Contents for MHVFR20TB NG

Page 1: ...m the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Fresh Air for Combustion and Ventilation section on page 4 of this manual WARNING I...

Page 2: ...able material on or near the appliance Never place any objects on the heater Due to high temperatures heater should be kept out of traffic and away from furniture and draperies Surface of heater becom...

Page 3: ...eep all air openings in heater clear free of debris or any blockage This will insure that enough air for proper combustion enters the heater 4 If heater shuts off do not relight until you provide fres...

Page 4: ...are excerpts from National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Com bustion and Ventilation All spaces in homes fall into one of the three following ventilation classifications 1 Unu...

Page 5: ...hr Vent Free Heater 20 000 Btu hr Total 60 000 Btu hr 4 Compare the maximum Btu hr the space can support with the actual amount of Btu hr used Example 51 800 Btu hr maximum Btu hr the space can suppor...

Page 6: ...sible provide greater clearances from the floor ceil ing and joining walls WARNING Rework worksheet adding the space of the adjoining unconfined space The combined space must have enough fresh air to...

Page 7: ...r will be located Make sure mounting bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can pr...

Page 8: ...ng bottom mounting screw into wall stud drill holes at marked locations using 9 64 drill bit 5 Re place heater onto mounting bracket 6 Place spacers between bottom mounting holes and wall anchor or dr...

Page 9: ...binet Ground Joint Union Equipment Shutoff Valve From Gas Meter 4 W C to 10 5 W C Pressure Tee Joint 1 8 NPT Plug Tap Cap Pipe Nipple Tee Joint 3 8 NPT Pipe Nipple Sediment Trap Test Gauge Connection...

Page 10: ...our gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If knob will not push in or turn by hand don t try to repair it call a qualified...

Page 11: ...Heater may need more frequent cleaning due to excess lent from carpeting bedding material pet hair etc Make sure grille guard is in place before running heater If screen or grille guard is removed fo...

Page 12: ...acuum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit ever 2 500 hours of operation or every three months We als...

Page 13: ...13 Installation Instructions and Owner s Manual Unvented Natural Gas Vent Free Room Heaters This page intentionally left blank...

Page 14: ...as regulator 6 Turn Control knob to pilot position When ignitor button is pressed in there is a spark at the ODS pilot but no ignition 1 Control knob not fully pressed in 2 Control knob not pressed in...

Page 15: ...ances see Figure 4 page 7 4 Clean burner orifice see Cleaning and Maintenance on pages 11 and 12 or replace burner orifice White powder residue forming within burner box or on adjacent walls or furni...

Page 16: ...rough Friday Please include the model number date of purchase and description of problem in all communication LIMITED WARRANTY Mr Heater Inc warrants its heaters and accessories to be free from defect...

Reviews: