Mr. Heater MHVFIH10LPT Operating Instructions And Owner'S Manual Download Page 5

5

Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

outdoors or spaces open to the outdoors. These 
include attics* and crawl spaces. Follow the National 
Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 
Air for Combustion and Ventilation for required size of 
ventilation grills or ducts.

*IMPORTANT:

 Do not provide openings for inlet or 

outlet into attic. If attic has a thermostat-controlled 
power vent, heated air entering the attic will activate 
the power vent.

IMPORTANT:

 Vent-free heaters add moisture to 

the air. Although this is benefi cial, installing heater 
in rooms without enough ventilation air may cause 
mildew to form from too much moisture. See Fresh 
Air for Combustion and Ventilation, pages 3 
through 5. 

INSTALLATION

NOTICE:

 This heater is intended for the use as 

supplemental heat. Use this heater along with your 
primary heating system. Do not install this heater as 
your primary heat source. If you have a central heating 
system, you may run system’s circulating blower while 
using heater. This will help circulate the heat throughout 
the house. In the event of a power outage, you can use 
this heater as your primary heat source for the duration 
of the outage. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 
heater, Gas furnace, Vented gas heater, Gas 
fi replace logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-
vent draws combustion air from the outdoors and 
vents to the outdoors.

Example:

Gas water heater 

40,000 Btu/hr

Vent Free   20,000 Btu/hr

Total   =60,000 

Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.

Example: 51,800 Btu/hr (maximum Btu/hr the   
 

space can support)

 

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confi ned 
space because the actual Btu/hr used is more than 
the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 
are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfi ned 
space, remove door to adjoining room or add 
ventilation grills between the rooms. See Ventilation 
Air From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Fig. 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfi ned. 

If actual Btu/hr used is less than the maximum 
Btu/hr the space can support, the space is an 
unconfi ned space. You will need no additional fresh 
air ventilation.

VENTILATION AIR

Ventilation from Inside Building

This fresh air would come from an adjoining unconfi ned 
space. When ventilation to an adjoining unconfi ned 
space, you must provide two permanent openings: one 
within 12” of the ceiling and one within 12” of the fl oor 
on the wall connecting the two spaces (see options 
1 & 2 of fi gure 2). You can also remove door into 
adjoining room (see option3, fi g 2). Follow the National 
Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 
Air for Combustion and Ventilation for required size of 
ventilation grills or ducts.

 WARNING:

 Rework worksheet, adding the space 

of the adjoining unconfi ned space. The combined 
space must have enough fresh air to supply all 
appliance in both spaces. 

Ventilation from Outdoors

If necessary provide extra fresh air by using ventilation 
grills or ducts. Connect these items directly to the 

Ventilation 
Gills into 
Adjoining 
Room - Op-
tion 1

Ventilation Gills into Ad-
joining Room - Option 2

12”

12”

Or remove 
door into 
Adjoining 
Room - 
Option 3

INLET 
AIR

OUTLET 
AIR

VENTILATION CRAWL SPACE

TO CRAWL 
SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 
ATTIC

OUTLET AIR

Figure 2

Figure 3.

Summary of Contents for MHVFIH10LPT

Page 1: ...pliance Do not touch an electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach yo...

Page 2: ...eld conversion is not permitted WARNING Do not use any accessory not approved for use with this heater WARNING Any change to this heater or its controls can be dangerous Do not place clothing or other...

Page 3: ...air for proper combustion enters the heater 4 If heater shuts off do not relight until you provide fresh outside air If heater keeps shutting off it requires servicing 5 Turn off and let cool before s...

Page 4: ...maller than defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by the methods described in the National Fuel Gas Code...

Page 5: ...space can support 60 000 Btu hr Actual amount of Btu hr used The space in the above example is a confined space because the actual Btu hr used is more than the maximum Btu hr the space can support You...

Page 6: ...18 inches above floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next...

Page 7: ...s firmly fastened to wall studs Attaching to Wall using Anchor For attaching mounting bracket to hollow walls wall areas between studs or solid walls concrete or masonry Note Wall anchors mounting scr...

Page 8: ...ff valve union and plugged 1 8 NPT tap Locate NPT tap within reach of test gauge hookup NPT tap must be upstream from heater see figure 11 A CSA AGA certified equipment shutoff valve with 1 8 NPT tap...

Page 9: ...front panel OPERATING YOUR HEATER FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury o...

Page 10: ...rth while depressed until pilot lights 7 Keep control knob depressed in for ten 10 seconds after lighting pilot If pilot goes out repeat steps 4 5 6 and 7 If pilot does not stay lit refer to Troublesh...

Page 11: ...ery 2 500 hours of operation or every three months We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed...

Page 12: ...turn more 5 a Contact local gas company b Clean ODS pilot see Cleaning and Maintenance page 11 6 Replace thermocouple 7 Replace Control valve Burner does not light after ODS pilot is lit 1 Burner orif...

Page 13: ...ng Gas Connections page 9 2 Replace control valve Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See WARNING statement at top of page 1 Take apart gas tubing a...

Page 14: ...bly w Thermocouple LP 1 20 80081 Thermostat Valve 1 8 80017 Burner Assembly 1 21 80019 Ignitor Pulse 1 9 80009 Orifice 1 22 80014 Ignitor Wire 1 10 80069 Burner Right Bracket 1 23 8001 1 Ignitor Brack...

Page 15: ...15 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater PAGE LEFT INTENTIONALLY BLANK...

Page 16: ...D WARRANTY Mr Heater warrants its heaters and accessories to be free from defects in material and workmanship for a period of 5 year from date of purchase Mr Heater will repair or replace this product...

Reviews: