Mr. Heater MHVFG30TB LP Operating Instructions And Owner'S Manual Download Page 5

5

Installation Instructions and Owner’s Manual

Unvented LP-Gas Vent Free Heaters

*Adjoining rooms are communication only if there 
are doorless passageways or ventilation grills be-
tween them.

DETERMINING THE TYPE OF HEATER 
LOCATION SPACE:

Use this method to determine if you have a confi ned or 
unconfi ned space.

Note:

 the space includes the room in which you 

install heater plus any adjoining rooms with doorless 
passageways or ventilation grills between the rooms.

1. Find the volume of the space by multiplying room 

length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.  
 

(Height) = 2592

If additional ventilation to adjoining room is supplied 
with grills or openings, add the volume of these rooms 
to the total volume of the space.

2. Divide the space volume by 50 cubic feet to deter-

mine the maximum Btu/hr the space can support.

Example: 2592 cu.ft. (volume of space) / 50 cu.ft. =  
 

51.8 or 51,800 (maximum Btu/hr the space  

 can 

support)

WARNING:

 If the area in which the heater may be 

operated is smaller than defi ned as an unconfi ned 
space or if the building is of unusually tight con-
struction, provide adequate combustion and ventila-
tion air by the methods described in the 

National 

Fuel Gas Code, NFPA 54/ ANSI Z223.1, 

Section 

5.3 or applicable local codes. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 
heater, Gas furnace, Vented gas heater, Gas fi re-
place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-
vent draws combustion air from the outdoors and 
vents to the outdoors.

Example: 

Gas water heater 

40,000 Btu/hr

 

 

Vent Free  

20,000 Btu/hr

 

 Total 

  =60,000 

Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.

Example:   51,800 Btu/hr (maximum Btu/hr the  
 

 

space can support)

 

 

60,000 Btu/hr (Actual amount of Btu/hr  

  

used)

The space in the above example is a confi ned 
space because the actual Btu/hr used is more than 
the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 
are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfi ned 
space, remove door to adjoining room or add venti-
lation grills between the rooms. See Ventilation Air 

From Inside Building (Figure 2).

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Figure 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfi ned. 

If actual Btu/hr used is less than the maximum Btu/
hr the space can support, the space is an uncon-
fi ned space. You will need no additional fresh air 
ventilation.

VENTILATION AIR

Ventilation from Inside Building

This fresh air would come from an adjoining unconfi ned 
space. When ventilation to an adjoining unconfi ned 
space, you must provide two permanent openings: one 
within 12” of the ceiling and one within 12” of the fl oor 
on the wall connecting the two spaces (see options 1 
& 2 of fi g. 2). You can also remove door into adjoin-
ing room (see option 3, fi g 2). Follow the National Fuel 
Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for 
Combustion and Ventilation for required size of ventila-
tion grills or ducts.

Figure 2.

Figure 3.

Ventilation 
Gills into 
Adjoining 
Room - 
Option 1

Ventilation Gills into 
Adjoining Room - Option 2

12”

12”

Or remove 
door into 
Adjoining 
Room - 
Option 3

INLET 
AIR

OUTLET 
AIR

VENTILATION CRAWL SPACE

TO CRAWL 
SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 
ATTIC

OUTLET AIR

Summary of Contents for MHVFG30TB LP

Page 1: ...rovisions for adequate combustion and ventilation air must be provided Refer to Fresh Air for Combustion and Ventilation section on page 4 of this manual WARNING Improper installation adjustment alter...

Page 2: ...to avoid burns or clothing igni tion Heater will remain hot for a time after shutdown Allow heater surfaces to cool before handling Young children should be carefully supervised when they are in the...

Page 3: ...eds outside ventilation air to run properly The Oxygen Depletion Sensor ODS safety shutoff system shuts down the heater if not enough fresh air is available See Fresh Air for Combustion and Ventilatio...

Page 4: ...excerpts from National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Com bustion and Ventilation All spaces in homes fall into one of the three following ventilation classifications 1 Unusuall...

Page 5: ...t Free Heater 20 000 Btu hr Total 60 000 Btu hr 4 Compare the maximum Btu hr the space can support with the actual amount of Btu hr used Example 51 800 Btu hr maximum Btu hr the space can support 60 0...

Page 6: ...enough fresh air to supply all ap pliance in both spaces Ventilation from Outdoors If necessary provide extra fresh air by using ventila tion grills or ducts Connect these items directly to the outdo...

Page 7: ...ill be located Make sure mounting bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can provi...

Page 8: ...tom Mounting Screws 1 Locate two bottom mounting holes These holes are near bottom on back panel of heater see figure 10 Figure 10 2 Mark screws locations on wall 3 Remove heater from mounting bracket...

Page 9: ...n Equipment Shutoff Valve From regulated LP tank 11 W C to 14 W C Pressure Tee Joint 1 8 NPT Plug Tap Cap Pipe Nipple Tee Joint 3 8 NPT Pipe Nipple Sediment Trap Test Gauge Connection Reducer Bushing...

Page 10: ...DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the ga...

Page 11: ...ding material pet hair etc Make sure grille guard is in place before running heater If screen or grille guard is removed for servicing it must be replaced prior to operating the heater push in or turn...

Page 12: ...ODS PILOT AND BURNER Use as vacuum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit ever 2 500 hours of operatio...

Page 13: ...ulator 6 Turn Control knob to pilot position When ignitor button is pressed in there is a spark at the ODS pilot but no ignition 1 Control knob not fully pressed in 2 Control knob not pressed in long...

Page 14: ...Figure 4 page 7 4 Clean burner orifice see Cleaning and Maintenance on pages 11 and 12 or replace burner orifice White powder residue forming within burner box or on adjacent walls or furni ture 1 Wh...

Page 15: ...15 Installation Instructions and Owner s Manual Unvented LP Gas Vent Free Heaters MHVFG30LP...

Page 16: ...any Mr Heater local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 800 251 0001 www mrheater com Our office hours are 8 00 AM 5 00 PM EST Monday through Frid...

Reviews: