Mr. Heater MHVFBF20 LPBT Operating Instructions And Owner'S Manual Download Page 5

Installation Instructions and Owner’s Manual

Unvented LP-Gas Vent Free Room Heaters

5

*Adjoining rooms are communication only if there 
are door less passageways or ventilation grills 
between them.

DETERMINING THE TYPE OF HEATER 
LOCATION SPACE:

Use this method to determine if you have a confi ned or 
unconfi ned space.

Note:

 the space includes the room in which you 

install heater plus any adjoining rooms with doorless 
passageways or ventilation grills between the rooms.

1. Find the volume of the space by multiplying room 

length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.  
 

(height) = 2592

If additional ventilation to adjoining room is supplied 
with grills or openings, add the volume of these rooms 
to the total volume of the space.

2. Divide the space volume by 50 cubic feet to deter-

mine the maximum Btu/hr the space can support.

Example: 2592 cu.ft. (volume of space) / 50 cu.ft. =  
 

51.8 or 51,800 (maximum Btu/hr the space  

 can 

support)

WARNING:

 If the area in which the heater may be 

operated is smaller than defi ned as an unconfi ned 
space or if the building is of unusually tight 
construction, provide adequate combustion and 
ventilation air by the methods described in the 

National Fuel Gas Code, NFPA 54/ ANSI Z223.1, 

Section 5.3 or applicable local codes. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 
heater, Gas furnace, Vented gas heater, Gas fi re-
place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-
vent draws combustion air from the outdoors and 
vents to the outdoors.

Example: 

Gas water heater 

40,000 Btu/hr

 

 

Vent Free  

20,000 Btu/hr

 

 Total 

  =60,000 

Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.

Example:   51,800 Btu/hr (maximum Btu/hr the  
 

 

space can support)

 

 

60,000 Btu/hr (Actual amount of Btu/hr  

  

used)

The space in the above example is a confi ned 
space because the actual Btu/hr used is more than 
the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 
are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfi ned 
space, remove door to adjoining room or add 
ventilation grills between the rooms. See Ventilation 

Air From Inside Building (Figure 2).

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Figure 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfi ned. 

If actual Btu/hr used is less than the maximum Btu/
hr the space can support, the space is an uncon-
fi ned space. You will need no additional fresh air 
ventilation.

VENTILATION AIR

Ventilation from Inside Building

This fresh air would come from an adjoining unconfi ned 
space. When ventilation to an adjoining unconfi ned 
space, you must provide two permanent openings: 
one within 12” of the ceiling and one within 12” of 
the fl oor on the wall connecting the two spaces (see 
options 1 & 2 of fi g. 2). You can also remove door into 
adjoining room (see option3, fi g 2). Follow the National 
Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 
Air for Combustion and Ventilation for required size of 
ventilation grills or ducts.

Figure 2.

Figure 3.

Ventilation 
Gills into 
Adjoining 
Room - 
Option 1

Ventilation Gills into 
Adjoining Room - Option 2

12”

12”

Or remove 
door into 
Adjoining 
Room - 
Option 3

INLET 
AIR

OUTLET 
AIR

VENTILATION CRAWL SPACE

TO CRAWL 
SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 
ATTIC

OUTLET AIR

Summary of Contents for MHVFBF20 LPBT

Page 1: ...tallation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional informa...

Page 2: ...IAL MEDIA WARNINGS IMPORTANT Read this owner s manual carefully and completely before trying to assemble operate or service this heater Improper use of this heater can cause serious injury or death fr...

Page 3: ...hr 2 931W shall not be installed in a bedroom or bathroom 3 Keep all air openings in heater clear free of debris or any blockage This will insure that enough air for proper combustion enters the heate...

Page 4: ...The following are excerpts from National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation All spaces in homes fall into one of the three following ventilation classific...

Page 5: ...Vent Free Heater 20 000 Btu hr Total 60 000 Btu hr 4 Compare the maximum Btu hr the space can support with the actual amount of Btu hr used Example 51 800 Btu hr maximum Btu hr the space can support...

Page 6: ...arances from the floor ceiling and joining walls WARNING Rework worksheet adding the space of the adjoining unconfined space The combined space must have enough fresh air to supply all ap pliance in b...

Page 7: ...bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can provide greater clearances from the fl...

Page 8: ...tom mounting holes and wall anchor or drilled hole 7 Hold spacer in place with one hand With the other hand insert mounting screw through bottom mounting hole and spacer Place tip of screw in opening...

Page 9: ...g into heater If sediment trap is not installed or is installed improperly heater may not run correctly Pressure Regulator Heater Cabinet Ground Joint Union Equipment Shutoff Valve From regulated LP t...

Page 10: ...ny phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you can not reach your gas supplier call the fire department C Use only y...

Page 11: ...a qualified service person of gas supplier for repairs If control knob does not pop up when released contact a qualified service person or gas sup plier for repairs 8 When the pilot is lit turn contr...

Page 12: ...e and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 psig This can be done by using a vacuum cleaner in the blow position usin...

Page 13: ...gulator 6 Turn Control knob to pilot position When ignitor button is pressed in there is a spark at the ODS pilot but no ignition 1 Control knob not fully pressed in 2 Control knob not pressed in long...

Page 14: ...ee Figure 4 page 7 4 Clean burner orifice see Cleaning and Maintenance on pages 11 and 12 or replace burner orifice White powder residue forming within burner box or on adjacent walls or furni ture 1...

Page 15: ...Installation Instructions and Owner s Manual Unvented LP Gas Vent Free Room Heaters 15...

Page 16: ...w Thermocouple 1 23 801 10 Fan Assembly 1 9 80009 Orifice 1 24 80049 Fan Switch 1 10 80073 Orifice Adapter 1 25 8001 1 Ignitor Module Mounting Bracket 1 11 80056 Regulator Mounting Bracket 1 26 80019...

Page 17: ...ple 1 23 801 10 Fan Assembly 1 9 80009 Orifice 1 24 80049 Fan Switch 1 10 80073 Orifice Adapter 1 25 8001 1 Ignitor Module Mounting Bracket 1 11 80055 Regulator Mounting Bracket 1 26 80019 Ignitor Pul...

Page 18: ...1 7 80079 Gas Input Elbow Adapter 1 20 801 10 Fan Assembly 1 8 80107 Regulator 1 21 8001 1 Ignitor Module Mounting Bracket 1 9 80021 Regulator Connection 1 22 80019 Ignitor Pulse 1 10 80055 Regulator...

Page 19: ...1 7 80079 Gas Input Elbow Adapter 1 30 801 10 Fan Assembly 1 8 80083 Regulator 1 31 8001 1 Ignitor Module Mounting Bracket 1 9 80021 Regulator Connection 1 32 80019 Ignitor Pulse 1 10 80055 Regulator...

Page 20: ...DERING INFORMATION PURCHASING Accessories may be purchased at any Mr Heater local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 800 251 0001 www mrheater co...

Reviews: