Mr. Heater HST45 Operating Instructions And Owner'S Manual Download Page 16

16

Mr. Heater | Gas-Fired Low-Intensity Infrared Heater

Operating Instructions and Owner’s Manual

Non-pressurized Outside Air Supply Duct

Outside Combustion Air Supply

The MHT tube heater is approved for installation with an outside air 
supply system. Some compounds such as halogenated hydrocarbons 
or other corrosive chemicals in the air can be drawn into the 
equipment and cause an accelerated rate of corrosion of some of the 
heater components. The use of such chemical compounds near the 
enclosure should be avoided.

IMpORTANT:

 If the building has a slight negative pressure or 

contaminants are present in the air, an outside combustion air supply 
to the heaters is strongly recommended.

For an outside air supply a three (3") inch O.D. single wall pipe may 
be attached to the heater. The duct may be up to twenty five (25') 
feet maximum length or two (2') feet minimum length with no more 
than two (2) elbows.

The air supply duct may have to be insulated to prevent 
condensation on the outer surface. The outside air terminal should 
be securely fastened to the outside wall by drilling four (4) holes in 
the outside flange; wood screws or bolts and expansion sleeves may 
be used to fasten terminal.

VERTICAL THROUGH THE ROOF

Intake Vent

3" Starting Collar 

¼” per ft. 

 

downwards

 

6" Min.

3" Dia. 

Single-Wall Pipe

 

Flashing

3' Min.

Vent Cap 
(Leslie VersaCap) 

Vertical Venting

Air For Combustion (Residential)

If indoor combustion air is to be supplied for a tightly enclosed area, 
one square inch of free area opening shall be provided below the 
heater for each 1,000 Btu/hr of heater input.

When outside air is used, the opening below the heater shall be one 
square inch of free area for each 4,000 Btu/hr of heater input. In 
contaminated atmospheres or high humidity areas, optional outside 
air for combustion is recommended.

Adequate clearances around the perforated fresh air plate must be 
maintained at all times. In larger open areas of buildings, infiltration 
normally is adequate to provide air for combustion.

Direct Outside Air For Combustion (Residential)

Outside combustion air should be supplied directly to the heater 
when the building is subject to negative pressure or contaminants 
are present in the building air. These contaminates include paints, 
solvents, corrosive vapors or any other foreign particles that may 
cause damage to the heater or result in poor combustion.

Outside combustion air can be brought directly to the heater by a 
3 inch diameter duct less than 25 feet long or equivalent. This is 
attached to a 3 inch starting collar that is fitted on inlet side of the 
control cabinet. An approved vent cap must be placed directly to the 
end of the outside combustion air inlet pipe. The combustion air 
inlet should be a minimum of 3 feet, either vertically or horizontally, 
from the flue vent termination. The air intake terminal must be 
located not less than one foot above grade. It is good installation 
practice to supply combustion air from the same pressure zone as 

the vent outlet.

In colder climates, where necessary, insulate the fresh air duct. Avoid 
locating the fresh air duct directly above the control box. Provide a 
capped cleanout T as necessary.

Summary of Contents for HST45

Page 1: ...any electrical switch do not use any phone in your building supplier If you cannot reach your gas supplier call the Fire Department Gas Fired Low Intensity Infrared Heaters approved for residential Ga...

Page 2: ...Echec pour se conformer aux precautions et aux in structions a fourni avec cet appareil de chauffage avoir pour resultat la mort blessure et la perte de propriete ou les dommages physiques serieuses d...

Page 3: ...the transfer of body oils from the hands to the surface of the reflector Vent Kit F102840 1 2 3 x 2 Pipe 26GA 2 1 36 x 3 B Vent 3 1 Gas Vent Top 3 4 1 Adj Wall Thimble 5 1 Storm Collar 6 1 3 Elbow 7...

Page 4: ...t energy downward to the space to be heated Heat Exchanger A U shaped tube through which the heated products of combustion pass Rear Movable Hanger Provides support for the heat exchanger and reflecto...

Page 5: ...ectrical Rating 120VAC 60Hz single phase 1 amp Connection 3 pin molded plug Gas Inlet Connection Connection Male NPT Gas Inlet Pressure The minimum inlet gas supply pressure for the purpose of input a...

Page 6: ...nting requirements for the MHT tube heater Specifies the national standards and applicable codes that apply to the gas electric and venting requirements Specifies the national standards and applicable...

Page 7: ...above the floor Minimum required safe distances to combustibles must be maintained from vehicles parked below the heater When installed over hoists the minimum required safe distances to combustible...

Page 8: ...as required Choose Location for Heater When selecting a suitable mounting location for the MHT tube heater it is important to consider the following 1 The heater must meet the minimum mounting height...

Page 9: ...ontal venting sections must slope away from the heater at a rate of per foot 5 The total length of vent pipe horizontal and vertical runs combined plus the length of the exterior termination must not...

Page 10: ...nted through the roof be sure to carefully review the roof option installa tion portion of this section Ensure that the selected mounting site will satisfy the measurement param eters vent length not...

Page 11: ...he gaskets The tube ends extend through the flanges to help with alignment 3 Using the four long and four short nuts from the bolt kit 02876 secure the tube set to the burner box As shown in the diagr...

Page 12: ...current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved d...

Page 13: ...ustible wall refer to the latest edition of the National Fuel Gas Code or the authority having jurisdiction In regions of the country where prevailing winds are consistently higher than 40 mph it may...

Page 14: ...is is to be constructed of galvanized sheet metal or other approved noncombustible corrosion resistant material as indicated by state and or local codes 2 For horizontal venting the vent lengths may b...

Page 15: ...ength should be shortened or insulated g For vent specifications all of the following conditions must be met The maximum equivalent length of vent pipe should be carefully observed A safety switch in...

Page 16: ...e area opening shall be provided below the heater for each 1 000 Btu hr of heater input When outside air is used the opening below the heater shall be one square inch of free area for each 4 000 Btu h...

Page 17: ...hown below To check system pressure a plugged 1 8 NPT tapping is required upstream of the manual gas shut off valve supplied with the heater Before connecting the heater to the supply system verify th...

Page 18: ...ns and burrs 3 Use LP resistant joint compound on all threads 4 Check the pipe and tube connections for leaks before placing heating equipment into service When checking for gas leaks use a soap and w...

Page 19: ...will then occur 8 Periodic visual check of burner flame while unit is in operation through sight glass in bottom of unit Section 6 MAINTENANCE Pre Season Maintenance Heater area to be kept clear and f...

Page 20: ...itch does not operate Igniter spark gap incorrect Try This Unplug heater power cord from the electrical outlet wait for a minimum of five seconds Plug heater cord back into outlet Unplug heater power...

Page 21: ...nlet pressure requirements contact the gas company Check for 24V across valve terminals Check Shutoff On Valve IF NO Check wiring between the ignition module and the valve Repair replace wires as requ...

Page 22: ...ters on the illustrations are keyed to the associated parts list I B A C J F H G D E ITEM PART NUMBER DESCRIPTION HST 35 HST 45 A 02808 Spark Electrode 1 1 B 02837 Ignition Wire 1 1 05795 Orifice MHT...

Page 23: ...CHASE REF ITEM DESCRIPTION A F202850 MHT 45NG Burner Box for F208850 F202851 MHT 45LP Burner Box for F202851 B F106250 MHT45 Tube Set Long C 06014 Hanger D 06016 Hanger Clamp E 06008 9 MHT 45 Reflecto...

Page 24: ...the claim Also supply us with the purchase date and the name and address of the dealer from whom you purchased our product The foregoing is the full extent of the responsibility of the Company There a...

Reviews: