Derating (60Hz)

The engine may be operated up to 5000 ft.
altitude and 95

o

F ambient temperature at the

Standby rating, wi thout derating. For
operation at higher altitudes and ambient
temperatures, the power should be derated
according to the following factors:

Altitude

Ambient

Temperature

Above 5000ft.

derate at 4%

per 1000 ft.

Above 95°F

derate at 1%

per 10°F

Inteligen Digital Genset Controller

Large graphic back-lit LCD display 128x64 pixel resolution

Automatic and manual starting and stopping

Phase sequence supervision

Automatic shutdown/alarm function

Input frequency 50-60 Hz

Parameters adjustable via PC or iG keyboard

Predefined and user definable configurations available.
One configuration includes set of inputs/outputs and parameters

Adjustable parameters for each configuration

6 LED indicators

Push buttons for simple control

4 programmable outputs (out of 20 functions selection)

4 binary configuration inputs

Lamp test during start up

Real time clock

Sealed membrane panel to IP65

180 x 113 mm front panel mounted case

Speed measurement from magnetic pickup

Oil pressure, Coolant temperature, Battery voltage and Fuel level
measurements

Running Hour Meter

All Generator metering, kVAr, kW, V1-V3, Hz, I1-I3, kWh, kVAh

Generator under/over voltage alarm/shutdown

Generator under/over frequency alarm/shutdown

Over Current alarm/shutdown

Warm up and cooling functions

Pre-lubrication function with timers

Adjustable crank attempts

Data logging

Remote communications (RS232/Modbus)

Digital Controller Features

Fuel System

Recommended Fuel

ASTM-D975-No.1 or No. 2-D

Filter Micron Size - 98% Efficiency

2

Total Fuel Flow

99 gal./hr. (374.7 L/Hr.)

Fuel Consumption

Diesel Fuel @ % of Load

gal/hr

L/hr

  25%

16.0

61

  50%

26.2

99

  75%

40.5

153

  100%

54.7

207

Cooling System

Exhaust Manifold Type

Dry

Radiator Design

Standard horizontal discharge

Coolant Capacity - Engine and Radiator

53 gal. (201 L)

Water Pump Design/Type

Belt Driven, Centrifugal

Coolant Flow

235 gal/min (889.5 L)

Heat Rejection to Coolant (Standby)

27860 BTU/min (29.5 kW)

Fan Horsepower

42.7 hp (32.0 kW)

Exhaust System

Standby

Prime

Exhaust Temperature at Rated kW

895 

o

F

(479.4 

o

C)

850 

o

F

(454.4 

o

C)

Exhaust Flow at Rated kW

6160 cfm

(174.3 m

3

/min)

5546 cfm

(157 m

3

/min)

Silencer Type

Critical

Maximum Allowable Backpressure

41 in/wc (10.2 kPa)

Exhaust Outlet Size at hook-up

2 x 8 in.

Summary of Contents for EGC-750C

Page 1: ... fast recovery from block loads and motor starting Full Load Acceptance Accepts100 ofstandbynameplateratinginonestep incompliance with NFPA para 5 13 2 6 Generator Control Panel InteligenTM vibration isolated controller Manual or remote engine start stop RS232 Modbus communication support Safety shutdowns Externally mounted emergency stop switch Generator mainline circuit breaker 100 rated electro...

Page 2: ...ge Regulated Brushless Voltage Regulation no load to full load 0 25 One Step Load Acceptance of rating per NFPA 110 100 Generator Efficiency at Full Load 93 Phase Sequence ABC L1 L2 L3 L L Harmonic Max Total 5 0 L L Harmonic Max Single 3 0 Amperage Voltage Phase Power Factor Continuous Amperes Standby Prime 120 208 Volt 3 0 8 2602 2082 277 480 Volt 3 0 8 1128 902 The EGC750C Sound Attenuated Gener...

Page 3: ...d measurement from magnetic pickup Oil pressure Coolant temperature Battery voltage and Fuel level measurements Running Hour Meter All Generator metering kVAr kW V1 V3 Hz I1 I3 kWh kVAh Generator under over voltage alarm shutdown Generator under over frequency alarm shutdown Over Current alarm shutdown Warm up and cooling functions Pre lubrication function with timers Adjustable crank attempts Dat...

Page 4: ...ight is approximate Wet weight does not include fuel 40 ft Container Generator Set Genset to Genset Paralleling Control System Base Load to Utility Paralleling Control System Custom Outlet Panels Rotary Voltage Selector Switch High Wye Low Wye Voltages Auxiliary Oil Reservoir with Level Control 15 gallon Centrifugal Oil Filter System Oil Pan Heater with Thermostat Alternator Strip Heater AC Batter...

Reviews: