DA7000SSA3 GENERATOR• OPERATION MANUAL — REV. #0 (02/13/19) — PAGE 33
Stopping the Engine (Normal Shutdown)
1. Place
main
circuit breaker (Figure 33) in the
OFF
position.
Figure 33. Main Circuit Breaker (OFF)
2. Place auxiliary
circuit breakers (Figure 34) in the
OFF
position.
Figure 34. Auxiliary Circuit Breakers (OFF)
3. Place idle control switch switch (Figure 35) in the
ON
position.
Figure 35. Idle Control switch (ON)
4. Let engine run at idle with no load for 3-5 minutes.
5. Place the starter switch key (Figure 36) in the
STOP
position and remove the key.
6.
Figure 36. Starter Switch (Stop Position)
7. Place fuel cock lever (Figure 37) in the
OFF
position.
Figure 37. Fuel Cock Lever (OFF)
8. Remove all load connections from the generator.
Emergency Shutdown
1. Place starter switch key (Figure 25) in
STOP
position.
Remove key. Place fuel cock lever (Figure 37)) in the
OFF
position.
OPERATION/SHUTDOWN