15
Program Description
Options
07
BTS
temperature
compensation ratio
0mV (Default)
The setting range is from
0mV to 60.0mV. Increment
of each short press is 0.1 mV.
The value will jump back to
0mV
after
60.0mV
is
achieved.
For each 12V battery, the
derated battery charging
voltage is followed the below
formula:
(Battery temperature – 25
o
C)
* BTS ratio.
08
Battery equalization
enable/disable
Disable (Default)
Enable
09
Battery equalization
voltage
14.60V(Default)
The setting range is from
12.00V to 15.50V.
If this program is
selected to modify,
the
changeable
figure
will
be
shown as below.
Increment of each short
press is 0.01V. The value will
jump back to 12.00V after
15.50V is achieved.
10
The
maximum
current of battery
equalization
15A (Default)
The setting range is from 5A
to 60A.
Increment of each short
press is 1A. The value will
jump back to 5A after 60A is
achieved.
11
Battery
equalized
time
60
minutes
(Default)
The setting range is from 5
minutes to 900 minutes.
Increment of each short
press is 5 minutes. The value
will jump back to 5 minutes
after 900 minutes are
achieved. .
12
Battery
equalized
timeout
120
minutes
(Default)
The setting range is from 5
minutes to 900 minutes.
Increment of each short
press is 5 minutes. The value
will jump back to 5 minutes
after 900 minutes are
achieved.
13
Equalization interval
30 days (Default)
The setting range is from 0
day to 90 days.