34
Troubleshooting your PV-Inverter
Inverter
Failure
Fault
Message
Diagnosis and Solution
PV Over
Voltage
(1) Check open PV voltage, see if it is too close to or
over 750VDC.
(2) If PV voltage is less than 750Vdc, and the
problem still occurs, please call service.
Consistent
Fault
(1) Disconnect PV(+) and PV(-) from the input, start
the unit again.
(2) If it does not work, please call service.
SCI Failure
Over
Temperature
(1) The internal temperature is higher than specified
normal value.
(2) Reduce the ambient temperature by some
appropriate and effective way.
(3) Or move Inverter to a cooler location.
(4) If it does not work, please call service.
Relay Failure
(1) Disconnect PV(+) and PV(-) from the input, start
the unit again.
(2) If it does not work, please call service.
DC INJ High
(1) Grid DC current higher than the permissible
value.
(2) Observe the faulty condition for 1 minute.
(3) If it does not restore to normal operation, please
call service.
EEPROM
Failure
(1) Disconnect PV(+) and PV(-) from the input, start
the unit again.
(2) If it does not restore to normal operation, please
call service.
High DC Bus
(1) Disconnect PV(+) and PV(-) from the input, start
the unit again.
(2) Check if L-LINE and N-Neutral are mistakenly
connected.
(3) If so, please call service.
Low DC Bus
(1) Disconnect PV(+) and PV(-) from the input, start
the unit again.
(1) If it does not work, please call service.
Ref 2.5V Fault
DC Sensor
Fault
GFCI Failure