![MPP Solar 1KVA-5KVA User Manual Download Page 29](http://html1.mh-extra.com/html/mpp-solar/1kva-5kva/1kva-5kva_user-manual_1843964029.webp)
27
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL
1KVA 24V
2KVA 24V
3KVA 24V
1KVA 48V
3KVA 48V
2KVA 24V Plus
3KVA 24V Plus
2KVA 48V Plus
3KVA 48V Plus
4KVA
5KVA
Input Voltage Waveform
Sinusoidal (utility or generator)
Nominal Input Voltage
120Vac or 230Vac
Low Loss Voltage
95Vac± 7V or 170Vac± 7V (UPS)
65Vac± 7V or 90Vac± 7V (Appliances)
Low Loss Return Voltage
100Vac± 7V or 180Vac± 7V (UPS);
70Vac± 7V or 100Vac± 7V (Appliances)
High Loss Voltage
140Vac± 7V or 280Vac± 7V
High Loss Return Voltage
135Vac± 7V or 270Vac± 7V
Max AC Input Voltage
150Vac or 300Vac
Nominal Input Frequency
50Hz / 60Hz (Auto detection)
Low Loss Frequency
40± 1Hz
Low Loss Return Frequency
42± 1Hz
High Loss Frequency
65± 1Hz
High Loss Return Frequency
63± 1Hz
Output Short Circuit Protection
Line mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency (Line Mode)
>95% ( Rated R load, battery full charged )
Transfer Time
10ms typical (UPS);
20ms typical (Appliances)
Output power derating:
When AC input voltage drops to 95V or
170V depending on models, the output
power will be derated.
120Vac model:
Input Voltage
Output Power
Rated Power
50% Power
65V
95V
140V
230Vac model:
Input Voltage
Output Power
Rated Power
50%
Power
90V
170V
280V