2

Smoke damper

rev 21-10

Description

Damper WXH is a single compartment smoke control damper; It’s a device which can be open or closed 

to control the flow of smoke and hot gasses into, from or within a duct for use in single compartment 

applications at elevated temperatures (600°C), which may be associated with smoke control ducts to 

EN1366-9:2008.

The function of the single compartment smoke control damper is to concentrate the fan pressure in the 

smoke reservoirs involved in the fire scenario.

The damper casing is made of galvanized steel with EPDM connection with leakage class C according with 

EN1751.

The damper has two different motorized versions depending on the relay response required: type AA 

(Automatic Activation) and type MA (Manual Activation, with fire rated motor covering box). The smoke 

damper is CE marked according to EN12101-8, tested according to EN1366-10 and classified according to 

EN13501-4. The damper is suitable for vertical and horizontal installation in single compartment smoke 

duct evacuation systems with maximum temperature of 600°C for 2 hours with smoke leakage class S at 

1500Pa negative pressure.

Declaration of performance

The damper is CE marked with the declaration of performance according to EN12101-8 as a circular smoke 
control damper single compartment with CPR nr. 1812-CPR-1189.

Manufacturer of the smoke damper:
MP3 S.r.l., via G. La Pira 9, 35012 Camposampiero (PD), Italy

Intended use

The damper is a part of a smoke and fire protection system that is designed to reach the following targets:
• 

Extract smoke for 2 hours during the fire

• 

Reduce temperatures during the fire

• 

Opens the blade and remove heat and smoke from a compartment in fire

• 

Closes the blade to prevent the spread of heat and smoke to a safe compartment

• 

Create an non-smoke layer

• 

Protect the property

This damper represents a part of the smoke and fire protection project whose main purpose is to be 

WXHU AA     

                                                                                         

WXHU MA

Summary of Contents for WXH Series

Page 1: ...CIRCULAR SERIES WXH 1500Pa Cert N 1812 CPR 1189 Technical Manual English WXH SINGLE COMPARTMENT SMOKE CONTROL DAMPER ...

Page 2: ...ng to EN1366 10 and classified according to EN13501 4 The damper is suitable for vertical and horizontal installation in single compartment smoke duct evacuation systems with maximum temperature of 600 C for 2 hours with smoke leakage class S at 1500Pa negative pressure Declaration of performance The damper is CE marked with the declaration of performance according to EN12101 8 as a circular smoke...

Page 3: ... installation both horizontal and vertical and with blade rotation axis both horizontal and vertical The fire classification obtained according to EN13501 4 2016 is According to the classification obtained according to Tables 1 and 3 level 3 and according to paragraph 6 3 2 2 of EN1366 10 2011 A1 2017 it is allowed to use single compartment smoke control dampers WXH In single compartment smoke exh...

Page 4: ... 115 298 9 5 407 12 0 560 115 298 11 0 407 13 5 630 115 298 12 5 407 15 Classification details E600 120 ved hod i S 1500Pa C10000 AA single E integrity Temperature Time ved Installation on duct penetrating a vertical wall hod Installation on duct penetrating a horizontal wall origin of fire is irrelevant Smoke leakage 5 m3 h m2 Maximum negative pressure Motor cycles use in combined smoke control a...

Page 5: ...et immediately Storage The goods should be stored inside and protected to prevent dust debris and humidity to damage the goods Before mounting Before starting the mounting of the damper it is necessary to inspect all components to make sure that they are correct according to the project documentation and to make sure they have not been damaged during transport or storage When handling the products...

Page 6: ...5 mm to support itself weight and to prevent damage to the gasket The damper must be installed on certifi ed and CE marked smoke control system Ø nom Minimum number of fasteners required to achieve sufficient strength 100 630 4 Mounting Technical data for the motors BLE motor BLE24 BLE230 Power supply AC DC 19 2 28 8 V 50 60 Hz AC 198 264 V 50 60 Hz Power consumption 7 5 W 5 W For wire sizing 9 VA...

Page 7: ...of several actuators possible Power consumption and switching thresholds must be observed 2 wire open close control The actuator is overload proof and can thus remain energized even at the end stops Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions The position of the damper blade can be read off on a mechanism position indicator The crank ...

Page 8: ... Periodic inspection and cleaning Periodic inspection shall be performed in accordance with the requirements of the law or by the building regulations or other local regulations In the absence of specific regulations or to their complement in accordance with point 8 3 of the EN 12101 8 standard it is recommended to carry out the following controlactivities at intervals of no more than 6 months exe...

Page 9: ...k that the smoke control damper is in the normal operating position Keep records of all inspections repair activities any problems encountered and their resolution This practice even when not mandatory is very useful in practice Disposal Disposal must be carried out in accordance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 Type WXH Circular smok...