 1MLWK25R0G 

3. 

FIRE RESISTANCE IN COMPLIANCE WITH EN 13501-3: 2005 (500 Pa)

 

INSTALLATION

MATERIAL

CLASSIFICATION

MECHANICAL 

ORIENTATION

DIMENSIONS

FIRE 

DIRECTION

WALL 

(Flush mounted 

in wall)

Aerated concrete 

Thickness   100 mm 

Density   550 kg/m

3

EI 120 S

Horizontal or vertical 

blade axis

100X200 to 

800X600

Indifferent

Plasterboard type 

98/48

EI 60 S

Horizontal or vertical 

blade axis

100X200 to 

800X600

Indifferent

Carreaux de platre

 

Gypsum blocks 

Thickness 70 mm

EI 90 S

Horizontal or vertical 

blade axis

100X200 to 

800X600

Indifferent

FLOOR 

(Flush-mounted 

with floor)

Reinforced concrete 

Thickness   150 mm 

Density   2200 kg/m

3

 

EI 180 S

Horizontal blade axis

100X200 to 

800X600

Indifferent

Aerated concrete 

Thickness   150 mm 

Density   650 kg/m

3

 

EI 120 S 

Horizontal blade axis 

100X200 to 

800X600 

Indifferent 

Aerated concrete 

Thickness   100 mm 

Density   650 kg/m

3

EI 90 S

Horizontal blade axis

100X200 to 

800X600

Indifferent

4.  DETAILED TECHNICAL DATA 

CONTROL 
MECHANISM

WK25B

WK25M

 
 
 

WK25 V/D 

 
Product type

 
Automatically controlled 
fire damper. 
Rectangular cross section. 

 

Automatically and remote 
controlled fire damper. 
Rectangular cross section.

 

Automatically and remote 
controlled fire damper. 
Rectangular cross section. 

 
Mandatory

Manual 

reset 

by 

direct 

action on the moveable part 
after closing when cold.

Manual reset by direct action 
on the moveable part after closing 
when cold. 
Safety position contact (limit switch) 
DCU/FCU (S2). 

Motorized  reset  after  closing 
when  cold  (can  be  local  or 
remote). 
Safety  position  contact  (limit 
switch). 

 

Safety options

 
Safety and standby 
position contacts (S2).

 

 

Operating mode

Without external energy.

Without  external  energy  for 
power 

supply 

input 

magnet 

during stand-by. 

With  external  energy  for  power 
supply 

interruption 

magnet 

during stand-by. 

With external energy. 

 

Control mode

 
Automatic: 

by 

fuse 

at 

70°C±7°C.

 

Automatic:  by  fuse  at  70°C  ±  7°C. 
Remote  control:  by  power  supply 
input or interruption on the magnet.

 

Automatic: by fuse at 72°C ± 7°C. 
Remote  control:  by  power  supply 
interruption. 

 

Installing position

 
Horizontal  or  vertical  blade 
axis.

 

Horizontal or vertical blade axis. 

 

Horizontal or vertical blade axis 

Air circulation 
direction

Indifferent.

Indifferent.

Indifferent. 

 

 

Solid Air

®

Luchtverdeeltechniek BV    Telefoon (020) 696 69 95    Fax (020) 691 30 62  www.solid-air.nl   Brandkleppen manual  06 2013

Solid Air

®

Luchtverdeeltechniek BV    Telefoon (020) 696 69 95    Fax (020) 691 30 62  www.solid-air.nl  06 2013

Brandkleppen manual

WH25
WH45

WK25
WK45

Solid Air

®

Luchtverdeeltechniek BV    Telefoon (020) 696 69 95    Fax (020) 691 30 62  www.solid-air.nl   Brandkleppen manual  06 2013

Solid Air

®

Summary of Contents for Solid Air WK25 D

Page 1: ...Brandkleppen manual Postbus 22756 1100 DG Amsterdam Z O Tel 31 0 20 696 69 95 Fax 31 0 20 691 30 62 mail solid air nl www solid air nl Solid Air Brandkleppen manual WH25 WH45 WK25 WK45 ...

Page 2: ... l y www mp3 italia it MAINTENANCE AND USE MANUAL WK25 Rectangular fire damper with low pressure drop 500 Pa Solid Air Luchtverdeeltechniek BV Telefoon 020 696 69 95 Fax 020 691 30 62 www solid air nl Brandkleppen manual 06 2013 Brandkleppen manual WH25 WH45 WK25 WK45 ...

Page 3: ...ism entirely outside wall Easy to install Maintenance free 2 RANGE OF DIMENSIONS Free area dm width 12 x height 37 10 000 with width and height in mm 4 3 2 5 6 1 7 1 Galvanised steel duct 2 Moveable blade in refractive material 3 Control mechanism 4 Connection flanges 5 Intumescent seal 6 Blade seal 7 Thermal fuse Solid Air Luchtverdeeltechniek BV Telefoon 020 696 69 95 Fax 020 691 30 62 www solid...

Page 4: ...tomatically and remote controlled fire damper Rectangular cross section Mandatory Manual reset by direct action on the moveable part after closing when cold Manual reset by direct action on the moveable part after closing when cold Safety position contact limit switch DCU FCU S2 Motorized reset after closing when cold can be local or remote Safety position contact limit switch Safety options Safet...

Page 5: ...mpliance with the technical specifications Use temperature 50 C maximum The WK25 fire damper is always tested in the frame of standardised supports in compliance with EN 1366 2 1999 table 3 4 5 The results obtained are valid for all similar support frames which have a thickness density and fire resistance equal or higher than that of the test Example of similar constructions aerated concrete wall ...

Page 6: ...concrete wall Wall hole dimension B 70mm H 70mm Damper installation 1 A rectangular hole sized B 70 mm x H 70 mm must be provided in the wall 2 Place the fire damper inside the prepared hole 3 Sealing with mortar class M10 or higher 4 Set up a mechanism clearance and access area 250mm Solid Air Luchtverdeeltechniek BV Telefoon 020 696 69 95 Fax 020 691 30 62 www solid air nl Brandkleppen manual 06...

Page 7: ... 5 mm on both sides to cover the rock wool On 70 mm light vertical modular plaster boards walls carreaux de plâtre Wall hole dimension B 50mm H 50mm Damper installation 1 A rectangular hole sized B 50 mm x H 50 mm must be provided in the wall 2 Position the damper in the hole on the wall 3 It is not necessary to insert any material simply cover the gap between wall and fire damper applying on both...

Page 8: ... single damper 7 CONTROL MECHANISMS WK25 MANUAL VERSION B M 70 C thermal fuse Manual switch off possible Manual resetting use the box lever turn anti clockwise 1 Manual switch off button 2 Control lever in safety position 3 Manual resetting turn the lever in the direction of the arrow WK25 B Automatically controlled mechanism with thermal fuse Solid Air Solid Air Luchtverdeeltechniek BV Telefoon 0...

Page 9: ...tic 24 48V DC electromagnetic coil Resetting Manual resetting Turn the lever anti clockwise Note For this remote control version the S2 micro switches are fitted as standard WK25 IN MOTORIZED VERSION V D Note For the motorized version micro switch is standard Siemens servo driven model To manually open the damper use the provided key to rotate clockwise until the indicator reaches a value of 90 an...

Page 10: ...LWK25R0G 8 DIMENSIONS BLADE EXPOSURE Solid Air Solid Air Luchtverdeeltechniek BV Telefoon 020 696 69 95 Fax 020 691 30 62 www solid air nl Brandkleppen manual 06 2013 Brandkleppen manual WH25 WH45 WK25 WK45 ...

Page 11: ... of the damper to the mains must only be done by a qualified electrician DCU single pole beginning of stroke contact C common NC normally closed lectronic mother board S0 25 for coil power supply and micro switches DCU single pole beginning of stroke contact NC normally closed NO normally open Coil power connector inal block for start and end contacts 10 mains must only be done by a qualified elec...

Page 12: ...ation 3 5 W In st by 2 W Input magnet P 3 4 W Motor 230V AC WK25 D Siemens GNA326 1ET In operation 4 5 W In st by 3 5 W Positioning contacts Standard 1mA 1A DC 5V AC 48V Standard 1mA 0 500mA DC 5V AC 48V Blade closing time Spring 1 s Motor 30 s Protection IP42 IP54 11 MAINTENANCE No special maintenance required Have the damper checked at least once a year After each intervention have the dust clea...

Page 13: ...12 1MLWK25R0G 12 EC declaration of conformity ...

Reviews: