Hardware Installation Procedure 

STEP 1: 

After unpacking the MGate MB3280, connect the power 
adapter. Make sure that the adapter is connected to an 
earthed socket outlet. 

STEP 2: 

Use a standard straight-through Ethernet cable to connect the 
MGate MB3280 to a network hub or switch. Use a cross-over 
Ethernet cable if you are connecting the gateway directly to a 
PC. 

STEP 3: 

Connect your device(s) to the MGate MB3280’s serial port. 

STEP 4: 

Place or mount the MGate MB3280. The unit may be placed 
on a horizontal surface such as a desktop, mounted on a DIN-
rail, or mounted on the wall. 

Wall or Cabinet Mounting 

Mounting the MGate MB3280 onto a wall 
requires two screws. The head of the screws 
should be 5.0 to 7.0 mm in diameter, the 
shaft should be 3.0 to 4.0 mm in diameter, 
and the length of the screws should be at 
least 10.5 mm. 

 

DIN-rail Mounting 

DIN rail attachments can be purchased separately to mount the MGate 
MB3280 on a DIN rail. 

Wall Mounting 

DIN-rail Mounting 

 

Termination Resistor and Adjustable Pull High/Low Resistors 

For some RS-485 environments, you may need to add termination 
resistors to prevent the reflection of serial signals. When using 
termination resistors, it is important to set the pull high/low resistors 
correctly so that the electrical signal is not corrupted. For each serial 
port, DIP switches are used for termination resistor and pull high/low 
resistor settings. To enable the 120 

 termination resistor, set switch 3 

on the assigned DIP switch to ON; set it to OFF (the default setting) to 
disable the termination resistor. To set the pull high/low resistors to 
150 K

 (the default setting), set switches 1 and 2 on the assigned DIP 

switch to the OFF position; set them both to ON for 1 K

 