Specifications
LAN
Ethernet
10/100 Mbps, RJ45, Auto MDI/MDIX
Protection
Built-in 1.5 kV magnetic isolation
Serial Interface
Interface
RS-232/422/485
No. of Ports
2 ports
Connector Type
DB9 (male)
Signals
RS-232:
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422:
Tx+, Tx-, Rx+, Rx-, GND
RS-485 (2-wire): Data+, Data-, GND
RS-485 (4-wire): Tx+, Tx-, Rx+, Rx-, GND
Serial Line Protection
15 kV ESD for all signals
RS-485 Data Direction
Patented ADDC™
Serial Communication Parameters
Parity
None, Even, Odd, Space, Mark
Data Bits
7, 8
Stop Bits
1, 2
Flow Control
RTS/CTS
Transmission Speed
50 bps to 921.6 Kbps
Software Features
Operation Mode
RTU Slave, RTU Master, ASCII Slave, ASCII Master
Utilities
MGate Manager
Multi-Masters and Multi-
Request
16 simultaneous TCP masters, 32 simultaneous requests for each TCP master
Summary of Contents for MGate MB3000 Modbus